| 2018-09-26 08:31:50 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PANEL SHOWN IS ONLY 150 BUS RATED, OCP FOR PV ARRAY IS | | | 50A? | | | | | | 50 X 125% + 125 = 187A 150 X 120% = 180A | | | | | | 705.12(D)(3)(2)(B) | | | (B) WHERE TWO SOURCES, ONE A UTILITY AND THE OTHER AN | | | INVERTER, ARE LOCATED AT OPPOSITE ENDS OF A BUSBAR THAT | | | CONTAINS | | | LOADS, THE SUM OF 125 PERCENT OF THE INVERTER(S) OUTPUT | | | CIRCUIT | | | CURRENT AND THE RATING OF THE OVERCURRENT DEVICE | | | PROTECTING THE | | | BUSBAR SHALL NOT EXCEED 120 PERCENT OF THE AMPACITY OF | | | THE | | | BUSBAR. THE BUSBAR SHALL BE SIZED FOR THE LOADS | | | CONNECTED IN | | | ACCORDANCE WITH ARTICLE 220. A PERMANENT WARNING LABEL | | | SHALL | | | BE APPLIED TO THE DISTRIBUTION EQUIPMENT ADJACENT TO | | | THE BACKFED | | | BREAKER FROM THE INVERTER THAT DISPLAYS THE FOLLOWING | | | OR | | | EQUIVALENT WORDING: |
|