| 2019-01-04 18:03:29 | ****CORRECTIONS**** |
| | ****REVISED 1/12/19*** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. RAS 117 CALCULATIONS WERE SUBMITTED, BUT ARE |
| | DESIGNED TO THE WRONG WIND SPEED, SEE MASTER PERMIT |
| | (170 RATHER THAN 180). A ROOF SUB PERMIT WAS SUBMITTED; |
| | CAN THIS DOCUMENT BE DELETED? |
| | |
| | 2. COMMENT FROM FIRST REVIEW: FBC 107, AN INDEX PAGE IS |
| | SUGGESTED. NOTE THAT, WITHOUT AN INDEX, IT IS VERY |
| | DIFFICULT TO FIND INFORMATION. FOR INSTANCE, LS001 |
| | WHICH INCLUDES INFORMATION NEEDED FOR REVIEW OF ALL |
| | OTHER SHEETS, IS AT THE END OF THE FILE DUE TO THE WAY |
| | THAT IT WAS NAMED; THIS IS TYPICALLY IN THE BEGINNING |
| | OR RIGHT AFTER CIVILS. |
| | |
| | 2ND REVIEW - DOCUMENT "101 - GI1000, 102 - GI1001", |
| | ETC. WERE UPLOADED. AS THE OTHER DOCUMENTS ARE A ZERO |
| | SERIES (001, 052, 060, ETC.) THE INDEX APPEARS AT THE |
| | END OF THE DOCUMENT. SINCE THE PURPOSE WAS TO MAKE THE |
| | PLAN EASIER TO REVIEW AND TO FIND INFORMATION, PLEASE |
| | RENAME SO IT APPEARS BEFORE THE OTHER SHEETS RATHER |
| | THAN AT THE END. |
| | |
| | 3-4. OK |
| | |
| | 4. COMMENT FROM FIRST REVIEW: DA121, FBC B 1017, SECOND |
| | TIER LEVEL, EXITING FOR THE STORAGE AREAS IS NOT CLEAR. |
| | REVISE PLAN TO SHOW EXIT ACCESS TRAVEL DISTANCE. |
| | |
| | 2ND REVIEW, LS003A & DA131, 209'4" AND 212' ARE NOTED |
| | AS THE TRAVEL DISTANCE BUT THE LOCATION OF THE EXIT IS |
| | NOT CLEAR. THE PATH OF EGRESS SHOWN ON THE PLAN APPEARS |
| | TO END IN THE MIDDLE OF AN OPEN STAIR. CLARIFY EXIT |
| | LOCATION AND TRAVEL DISTANCE. LS003A DOES NOT APPEAR TO |
| | SHOW THE EXIT. IF THIS IS COVERED UNDER AN EXCEPTION, |
| | PLEASE REVISE PLAN TO INCLUDE. |
| | |
| | 5. COMMENT FROM FIRST REVIEW: DA131, FBC B 1017, THIRD |
| | TIER LEVEL, EXITING FOR THE STORAGE AREAS IS NOT CLEAR. |
| | REVISE PLAN TO SHOW EXIT ACCESS TRAVEL DISTANCE. |
| | |
| | 2ND REVIEW, LS003A, DA131, 209'4" AND 212' ARE NOTED AS |
| | THE TRAVEL DISTANCES. THIS IS THE SAME AS 2ND FLOOR BUT |
| | BOTH APPEAR TO TRAVEL THROUGH AN UNPROTECTED STAIR, NOT |
| | CLEAR WHERE 209'4" ENDS FOR EACH STAIR. IF 209'4" IS |
| | THE DISTANCE FROM 2ND FLOOR STORAGE ROOM TO AN EXIT, |
| | AND 3RD FLOOR USES THE SAME TRAVEL PATH BUT IS ONE |
| | FLOOR HIGHER, IT APPEARS THAT THE 3RD FLOOR NUMBER |
| | SHOULD BE A LARGER NUMBER. |
| | |
| | 6-7. OK |
| | |
| | 8. PRECAST ENGINEERING IN SUPPORTING DOCUMENTS, |
| | DELEGATED ENGINEERING IS TO BE REVIEWED BY SEOR, |
| | FAC61G15. |
| | |
| | 2ND REVIEW, RESPONSE LETTER STATES TO REFER TO REVIEW |
| | LETTER; UNABLE TO LOCATE. PLEASE PROVIDE OR ADVISE AS |
| | TO FILE NAME. |
| | |
| | 9. OK |
| | |
| | NEW COMMENT: |
| | |
| | 10. PER OUR DISCUSSION - SUBMIT THE DELEGATED |
| | ENGINEERING AND ENGINEERED SHOP DRAWINGS AS A |
| | SUBMITTAL. SUBMIT THE MISSING PAGE DS502 AS A REVISION |
| | TO 18060764. IT IS MY UNDERSTANDING THAT THIS IS IN |
| | PROGRESS (PENDING CITY STAFF GENERATING A PROJECTDOX |
| | SUBMITTAL AND INVIDATION TO UPLOAD). |
| | |
| | 11. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING |
| | PROVISOS: |
| | |
| | A. A SEPARATE ROOF PERMIT IS REQUIRED. PRIOR TO |
| | INSTALLATION, SUBMIT ROOF PERMIT APPLICATION WITH |
| | PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND |
| | ENGINEERING FOR ENHANCED FASTENING IF APPLICABLE. |
| | |
| | B. COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY |
| | DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING |
| | DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION. |
| | |
| | |