| Date |
Text |
| 2018-11-05 17:26:04 | FAILED |
| | |
| | 1) PROVIDE A SITE PLAN OR SURVEY SHOWING THE BUILDING |
| | SETBACKS. |
| | |
| | 2) THE ROOF DOES NOT MATCH THE PLANS APPROVED BY THE |
| | CITY COMMISSION. THE LOWEST LEVEL OF ROOF HAS BEEN |
| | REMOVED FROM THE PERMIT PLANS. IN ORDER TO REMOVE THIS |
| | FEATURE, THE CITY COMMISSION IS REQUIRED TO APPROVE AS |
| | PART OF A REVISED LEVEL III SITE PLAN REVIEW. |
| | |
| | 3) THE PLANS ARE UNCLEAR TO THE DEPTH OF THE HORIZONTAL |
| | AND VERTICAL MULLIONS. THE APPROVED PLANS WERE TO |
| | EXPAND THE LOBBY WITH THE SAME DEPTH OF THE MULLIONS. |
| | SHEET DA303 SEEMS TO INDICATE HORIZONTAL MULLION DEPTH, |
| | BUT DOES NOT GIVE DETAILS ON THE DEPTH, NOR HOW IT |
| | COMPARES TO THE EXISTING MULLION DEPTH. PROVIDE |
| | INFORMATION TO VERIFY THAT THE HORIZONTAL AND VERTICAL |
| | MULLIONS ARE THE SAME AS EXISTING. |
| | |
| | 4) THE MECHANICAL PLANS SHOW NEW ROOFTOP EQUIPMENT. IN |
| | ACCORDANCE WITH THE CITYPLACE DRI, PLEASE PROVIDE |
| | VERIFICATION THAT ALL ROOFTOP MECHANICAL EQUIPMENT, |
| | INCLUDING BUT NOT LIMITED TO SUCH ITEMS AS PUBLIC AND |
| | PRIVATE UTILITY SERVICE CONNECTIONS; HEATING, |
| | VENTILATING, AND AIR CONDITIONING SYSTEMS; |
| | COMMUNICATIONS DEVICES; AND RELATED EQUIPMENT, SHALL BE |
| | SCREENED FROM PUBLIC VIEW THROUGH ANY COMBINATION OF |
| | LANDSCAPING, WALLS AND EQUIPMENT LOCATION. PLEASE |
| | PROVIDE PLANS OR OTHER EVIDENCE THAT THE NEW ROOFTOP |
| | MECHANICAL EQUIPMENT WILL BE SCREENED FROM PUBLIC VIEW. |
| | |