| 2018-11-02 16:34:04 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. ROOF PRODUCT APPROVAL WAS SUBMITTED; FBC 107 PRODUCT |
| | APPROVALS ARE TO BE REVIEWED BY DESIGNER OF RECORD |
| | PRIOR TO SUBMITTAL TO THE CITY. NOTE THAT THE ASSEMBLY |
| | DOES NOT MEET THE DESIGN PRESSURES FOR ZONES 2 & 3, SO |
| | RAS 117 CALCULATIONS ARE REQUIRED. |
| | |
| | THIS CAN BE ADDRESSED AT THIS TIME OR WILL BE A PROVISO |
| | ITEM, SUBMIT WITH ROOF PERMIT APPLICATION, REVIEW |
| | REQUIRED AT THAT TIME. |
| | |
| | 2. FBC 107, AN INDEX PAGE IS SUGGESTED. NOTE THAT, |
| | WITHOUT AN INDEX, IT IS VERY DIFFICULT TO FIND |
| | INFORMATION. FOR INSTANCE, LS001 WHICH INCLUDES |
| | INFORMATION NEEDED FOR REVIEW OF ALL OTHER SHEETS, IS |
| | AT THE END OF THE FILE DUE TO THE WAY THAT IT WAS |
| | NAMED; THIS IS TYPICALLY IN THE BEGINNING OR RIGHT |
| | AFTER CIVILS. |
| | |
| | 3. LS001, LS002, A TEMPORARY LIFE SAFETY PLAN WAS |
| | PROVIDED FOR TWO LEVELS. PROVIDE A LIFE SAFETY PLAN FOR |
| | FINISHED CONSTRUCTION, FBC B CHAPTER 10. THIS SHOULD |
| | INCLUDE THE NEW OCCUPANT LOAD FBC B 1004. |
| | |
| | 4. LS001, NOTES FOR 508, 508.4 ARE NOT CLEAR AS TO |
| | DESIGN INTENT AND WHICH NOTE IS APPLICABLE TO THE |
| | STORAGE AREAS. I COULD NOT FIND OCCUPANCY |
| | CLASSIFICATION FOR THE STORAGE AREAS; REVISE TO |
| | INCLUDE. IT APPEARS THAT THE STORAGE MAY BE S2, WHICH |
| | PER THE NOTE 508.4, SEPARATION IS REQUIRED. |
| | |
| | 4. DA121, FBC B 1017, SECOND TIER LEVEL, EXITING FOR |
| | THE STORAGE AREAS IS NOT CLEAR. REVISE PLAN TO SHOW |
| | EXIT ACCESS TRAVEL DISTANCE. |
| | |
| | 5. DA131, FBC B 1017, THIRD TIER LEVEL, EXITING FOR THE |
| | STORAGE AREAS IS NOT CLEAR. REVISE PLAN TO SHOW EXIT |
| | ACCESS TRAVEL DISTANCE. |
| | |
| | 6. LS001, REVISE DESCRIPTION OF WORK TO INCLUDE THE 2ND |
| | AND 3RD TIER STORAGE AREAS, FBC 107. |
| | |
| | 7. DA121, FBC B 713, 2 HR FIRE RATED CHASE IS SHOWN; |
| | REVISE PLAN TO INDICATE WHICH ASSEMBLY IS PROPOSED. |
| | |
| | 8. PRECAST ENGINEERING IN SUPPORTING DOCUMENTS, |
| | DELEGATED ENGINEERING IS TO BE REVIEWED BY SEOR, |
| | FAC61G15. |
| | |
| | 9. PROVIDE A SITE PLAN SHOWING COMPLIANCE WITH FBC B |
| | TABLES 602, 705.8. |
| | |
| | 10. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING |
| | PROVISOS: |
| | |
| | A. A SEPARATE ROOF PERMIT IS REQUIRED. PRIOR TO |
| | INSTALLATION, SUBMIT ROOF PERMIT APPLICATION WITH |
| | PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND |
| | ENGINEERING FOR ENHANCED FASTENING IF APPLICABLE. |
| | |
| | B. COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY |
| | DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING |
| | DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION. |
| | |
| | |