| 2018-10-02 13:51:16 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC |
| | 107.3.5; FBC RE E3706.2, E3902 |
| | |
| | 2. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE |
| | CORRECTION. NEC 210.12; FBC RE E3902.16 |
| | |
| | 3. RECEPTACLES IN KITCHEN REQUIRE GFCI PROTECTION. |
| | PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.6 |
| | |
| | 4. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL |
| | HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| | 210.8(A)(9); FBC RE E3902.9 |
| | |
| | 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| | 210.8(D); FBC RE E3902.10 |
| | |
| | 6. PROVIDE LOCATION OF PANEL ON PLAN. FBC 107.2.1 |
| | |
| | 7. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED |
| | GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL |
| | SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON |
| | THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE |
| | LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B), |
| | FBC RE E3903.3 |
| | |
| | 8. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 |
| | |
| | 9. NO DISCONNECT FOR W/H 422.30 NEC PROVIDE CORRECTION. |
| | |
| | 10. NO TANKLESS WATER HEATER IN LOAD CALC, PROVIDE |
| | ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. NEC 220; |
| | FBC RE E3602.2 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |