| 2018-09-30 13:49:13 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. REMOVE REFERENCES TO NEC 2011, WHICH IS NOT THE |
| | CURRENT CODE IN EFFECT. FBC PREFACE (SEE ABOVE ALSO) |
| | 2. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS |
| | INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES. |
| | SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION. |
| | PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902 |
| | 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10; FBC RE E3606.3 |
| | 4. PROVIDE AIC RATING OF PANEL. NEC 110.3, 110.9; FBC |
| | RE E3606.3 |
| | 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| | 210.8(D); FBC RE E3902.10 |
| | 6. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| | 7. SHOW LOCATION OF ELECTRICAL SERVICE ON PLAN |
| | INCLUDING LOCATION OF METER CAN AND INTERIOR PANEL. WPB |
| | FBC 107.2.1 |
| | 8. PROVIDE ACCURATE LOAD CALCULATION FOR RESIDENCE |
| | BASED ON FORMAT IN FBC RESIDENTIAL. FBC RE E3602.2 |
| | 9. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM |
| | BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET |
| | FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE |
| | R314.3(4), NFPA 72:29.8.3.4 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |