| 2019-01-03 10:45:02 | 1) SUBMIT A WATER RISER DIAGRAM FOR THE PLUMBING WORK |
| | THAT HAS BEEN DONE. WPB AMEND. TO 2017 FBC SEC. |
| | 107.3.5.1.3. 2ND REQUEST. |
| | 2) IS THIS TOILET ROOM HANDICAP ACCESSIBLE? IF SO, |
| | SUBMIT DETAILS FOR THE WATER CLOSET, LAVATORY, HAND |
| | DRYER, GRAB BARS, TOILET PAPER DISPENSER, ETC. WPB |
| | AMEND. TO FBC SEC. 107.2.1. 2ND REQUEST. |
| | 3) INDICATE THE WALL AND FLOOR FINISHES OF THE TOILET |
| | ROOM ON THE PLANS. WALLS WITHIN TWO FEET OF WATER |
| | CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBANT |
| | SURFACE, TO A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE |
| | FLOOR PER 2017 FBC SEC. 1210.2.2. THE FLOOR FINISH |
| | MATERIAL SHALL HAVE A SMOOTH, HARD NONABSORBANT SURFACE |
| | AND THE INTERSECTIONS OF SUCH FLOORS WITH WALLS SHALL |
| | COMPLY WITH 2017 FBC SEC.1210.2.1. 2ND REQUEST. |
| | 4) THE SUBMITTED PLAN SHOWS THE REMOVAL OF A MOP SINK |
| | AND A URINAL. THE MOP SINK IS A REQUIRED FIXTURE PER |
| | TABLE 403.1 OF THE PLUMBING CODE AND REMOVING THIS |
| | FIXTURE MAY BE CREATING A PLUMBING CODE VIOLATION. IS |
| | THERE ANOTHER MOP SINK IN THE BUILDING? THE URINAL MAY |
| | ALSO BE REQUIRED. SUBMIT THE TOTAL OCCUPANT LOAD FOR |
| | THIS RESTAURANT AND THE TOTAL NUMBER OF EXISTING WATER |
| | CLOSETS AND LAVATORIES FOR THE MALES AND THE TOTAL |
| | NUMBER OF WATER CLOSETS AND LAVATORIES FOR THE FEMALES. |
| | 5) IF THIS TOILET ROOM IS HANDICAP ACCESSIBLE, SHOW THE |
| | REQUIRED CLEAR FLOOR SPACE FOR THE WATER CLOSET AND THE |
| | LAVATORY ON THE FLOOR PLAN. 2017 FBC-ACCESS. SEC.604.3 |
| | (WATER CLOSETS) AND SEC. 606.2 (LAVATORIES). |
| | 6) IS THIS TOILET ROOM SERVING THE MALE OR FEMALE |
| | GENDER? INDICATE SUCH ON THE PLAN. |
| | 7) THE SANITARY RISER DOES NOT CORRELATE WITH THE FLOOR |
| | PLAN AND THE PLUMBING CANNOT BE INSTALLED AS DRAWN. |
| | 8) TEMPERED WATER IS REQUIRED AT THE LAVATORY AND HOT |
| | WATER WILL BE REQUIRED AT THE MOP SINK. 2017 FBC- |
| | PLUMBING SEC.607.1, 416.5. |
| | |
| | |
| | NOTE: ANY NEW PLUMBING WORK THAT HAS BEEN COVERED BY |
| | DRYWALL OR CONCRETE SHALL BE EXPOSED FOR INSPECTION. |
| | WPB AMEND. TO FBC SEC. 110.6. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |