Plan Review Notes
Plan Review Notes For Permit 18090922
Permit Number 18090922
Review Stop B
Sequence Number 2
Notes
Date Text
2019-01-09 10:29:302017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18090922
 ADD: 6803 S. DIXIE HWY.
 CONT: ATLANTIC GENERAL CONTRACTING INC.
 TEL: 561-434-4171
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. JAN. 09/2019
 ACTION: DENIED
  
 1) PLEASE NOTE THE PRIME PERMIT 19090922 IS FOR THE
 REMOVAL OF AN EXISTING INTERIOR CLOSET AND REPLACE
 DRYWALL. THE SUBMITTED PLANS ARE FOR A NEWLY
 RECONFIGURATION RESTROOM. PLEASE EXPLAIN IF THERE IS A
 CHANGE IN THE SCOPE OF WORK, IF SO PLEASE CHANGE THE
 SCOPE OF WORK ON THE PERMIT APPLICATION AS
 WELL.107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) THERE IS A CLOSED PERMIT 18010296 FOR THE CONVERSION
 OF A RESTROOM TO BE A HANDICAPPED RESTROOM.
 ON THAT PERMIT AND ON THIS PROPOSED PERMIT NEITHER
 STATE HOW MANY RESTROOMS THERE ARE IN THIS RESTAURANT,
 NOR HOW MANY ARE ACCESSIBLE RESTROOMS, NOR IF THEY ARE
 UNISEX RESTROOMS WITH THE APPROPRIATE SIGNAGE?
 2017 FBC-B TABLE 2902.1 MINIMUM NUMBER OF REQUIRED
 PLUMBING FIXTURES (FOOTNOTE A) (SEE SECTIONS 2902.1.1
 AND 2902.2)
 2017 FBC-ACCESSIBILITY CODE SECTION 213.1. WHERE TOILET
 FACILITIES AND BATHING FACILITIES ARE PROVIDED, THEY
 SHALL COMPLY WITH 213.
  
 3) PLEASE NOTE THERE JOBSITE PICTURES THAT ALL DRYWALL
 ON THE WALLS WAS REMOVED. PLEASE SHOW COMPLIANCE WITH:
 3A) 2017 FBC-B SECTION 2509.1 WET AREAS. PUBLIC TOILET
 WALLS SHALL CONFORM TO SECTION 1210.2.
  
 3A)(1) FBC-B 1210.2.1 FLOORS AND WALL BASES. IN OTHER
 THAN DWELLING UNITS, TOILET, BATHING AND SHOWER ROOM
 FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH FLOORS
 WITH WALLS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 VERTICAL BASE THAT EXTENDS UPWARD ONTO THE WALLS NOT
 LESS THAN 4 INCHES.
  
 3A)(2) FBC-B 1210.2.2 WALLS AND PARTITIONS. WALLS AND
 PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE
 FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, THE
 MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS
 NOT ADVERSELY AFFECTED BY MOISTURE.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  