| Plan Review Notes For Permit 18090922 |
| Permit Number |
18090922 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-11-01 15:56:57 | 1) THE SCOPE OF WORK NOTED ON THE APPLICATION AND ALSO | | | IN THE LETTER FROM SPEEDY ROOTER DOES NOT CORRELATE | | | WITH THE PHOTOS TAKEN BY THE FIELD INSPECTOR. THIS | | | APPEARS TO BE A COMPLETE ALTERATION OF AN EXISTING | | | STORAGE ROOM INTO A TOILET ROOM. SUBMIT A COPY OF THE | | | EXISTING FLOOR PLAN AND OF THE PROPOSED FLOOR PLAN. WPB | | | AMEND. TO 2017 FBC SEC. 107.3.5.1.3. | | | 2) SUBMIT A WATER AND SANITERY RISER DIAGRAM FOR THE | | | PLUMBING WORK THAT HAS BEEN DONE. WPB AMEND. TO 2017 | | | FBC SEC. 107.3.5.1.3. | | | 3) SHOW THE DIMENSIONS OF THE TOILET ROOM ON THE PLANS | | | (L X W ). | | | 4) IS THIS TOILET ROOM HANDICAP ACCESSIBLE? IF SO, | | | SUBMIT DETAILS FOR THE WATER CLOSET, LAVATORY, HAND | | | DRYER, GRAB BARS, TOILET PAPER DISPENSER, ETC. | | | 5) SUBMIT TWO COPIES OF PROFESSIONALLY DRAWN PLANS THAT | | | BEAR THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE | | | FOR THE DESIGN. | | | 6) INDICATE THE WALL FINISHES OF THE TOILET ROOM ON THE | | | PLANS. WALLS WITHIN TWO FEET OF WATER CLOSETS SHALL | | | HAVE A SMOOTH, HARD, NONABSORBANT SSURFACE, TO A HEIGHT | | | OF NOT LESS THAN 4 FEET ABOVE THE FLOOR PER 2017 FBC | | | SEC. 1210.2.2. | | | | | | NOTE: ANY NEW PLUMBING WORK THAT HAS BEEN COVERED BY | | | DRYWALL OR CONCRETE SHALL BE EXPOSED FOR INSPECTION. | | | WPB AMEND. TO FBC SEC. 110.6. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|