| 2019-01-15 15:00:16 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18090922 |
| | 1/15/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE A SCOPE OF WORK FOR MECHANICAL, AND CLARIFY |
| | IF THE EXHAUST FAN SHOWN ON THE DRAWINGS IS NEW OR |
| | EXISTING. IT APPEARS A NEW EXHAUST FAN WAS INSTALLED. |
| | PLEASE PROVIDE AN EQUIPMENT SCHEDULE FOR THE FAN AND |
| | SHOW THE EXHAUST DUCT RUN AND TERMINATION LOCATION. |
| | |
| | 2) PLEASE NOTE THAT ALL PLANS SHALL BE DRAWN BY A FL. |
| | LICENSED ARCHITECT OR ENGINEER IN ACCORDANCE WITH |
| | SECTION 107.1 WPB. CONTRACTOR DRAWN PLANS MUST BEAR THE |
| | SIGNATURE OF THE CONTRACTOR- SECTION 107.2.1 WPB. THE |
| | SUBMITTED PLANS DRAWN BY ON TARGET HOME DESIGNS ARE NOT |
| | ACCEPTABLE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |