| 2018-10-30 11:58:31 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 18090907 |
| | ADD: 5865 CARIBBEAN BLVD. BLDG. 18/ UNIT 1 |
| | CONT: BEST BUILDING CONCEPTS/ CRC1328815 |
| | TEL: 561-294-8255 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. OCT. 29/ 2018 |
| | ACTION: DENIED |
| | |
| | 1) THE SCOPE OF WORK INDICATED UNDER THIS PERMIT IS |
| | BEYOND THE SCOPE OF YOUR LICENSE (CRC1328815). PLEASE |
| | REVIEW 2018 FLORIDA STATUTE 489.105 ( C ). RESIDENTIAL |
| | CONTRACTOR MEANS A CONTRACTOR WHOSE SERVICES ARE |
| | LIMITED TO CONSTRUCTION, REMODELING, REPAIR, OR |
| | IMPROVEMENT OF ONE-FAMILY, TWO-FAMILY, OR THREE-FAMILY |
| | RESIDENCES NOT EXCEEDING TWO HABITABLE STORIES ABOVE NO |
| | MORE THAN ONE UNINHABITABLE STORY AND ACCESSORY USE |
| | STRUCTURES IN CONNECTION THEREWITH. |
| | |
| | 2) MISSING INFORMATION. 107.3.5 MINIMUM PLAN REVIEW |
| | CRITERIA FOR COMMERCIAL BUILDINGS. |
| | 107.3.5.1FLOOR PLANS. |
| | 107.3.5.1.8 WIND REQUIREMENTS. |
| | 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 2. RISK CATEGORY. |
| | |
| | 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. |
| | |
| | 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | |
| | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | 3) PRODUCT APPROVALS CAN NOT BE REVIEWED UNTIL THE WIND |
| | DESIGN CRITERIA IS GIVEN. 107.2.1.3. ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 4) THE PLANS DOES NOT STATE IF THIS IS A 1ST STORY UNIT |
| | OR 2ND STORY UNIT. IF A 2ND STORY UNIT THEN SHOW |
| | COMPLIANCE WITH: BLDG TYPE: TYPE I/ TYPE II FLOOR |
| | INSULATION (FBC-B 2017) |
| | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | 4A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 4B) FBC-B 2017 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 4C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | TYPE III-TYPE V CONSTRUCTION: |
| | FBC-B-2014 720.2 CONCEALED INSTALLATION. INSULATING |
| | MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF |
| | ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD |
| | INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX |
| | OF NOT MORE THAN 450. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | |