2018-10-18 13:24:31BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- CLARIFY PURPOSE OF STAIRS. ARE THESE STAIRS GOING TO
 BE PART OF THE EGRESS REQUIREMENTS OR CIRCULATION.
 PROPER REVIEW CAN NOT BE DONE WITHOUT PROPOSED USE.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2- PER CONVERSATION WITH RODNEY NORTH GREEN
 (ARCHITECT), THIS BUILDING HAS A RESTAURANT. ACCORDING
 TO CITY RECORDS AND PALM BEACH COUNTY PROPERTY
 APPRAISER THIS BUILDING IS WAREHOUSE NOT RESTAURANT. IS
 THIS A CHANGE OF OCCUPANCY?. PROVIDE PROOF OF CHANGE
 OCCUPANCY. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- REVISE/CLARIFY CODE INFORMATION ON SHEET A-1:
 A) FBC 2017 IS THE 6TH EDITION NOT 5TH EDITION. CHAPTER
 553 F.S.
  
 B) THIS IS NOT ALTERATION LEVEL 1. SEE CHAPTER 5 OF
 FBC-EXISTING BUILDING AND PROVIDE THE CORRECT
 CLASSIFICATION.
  
 C) CLARIFY OCCUPANCY: OCCUPANCY S-2?. COORDINATE WITH
 ITEM #2 ABOVE. SEC. 107.2.1 CITY AMENDMENTS.
  
 D) CONSTRUCTION TYPE SPECIFIED IS CONSTRUCTION TYPE
 II-B. THIS TYPE OF CONSTRUCTION IS FOR NONCOMBUSTIBLE
 MATERIALS. SEC. 602.2 FBC. STAIRS DETAILS ARE FOR WOOD
 STAIRS. NEED TO COORDINATE WITH ITEM #1 AND #2 ABOVE.
 WOOD STAIRS MAY NOT BE ALLOWED. REVISE/CLARIFY AS
 REQUIRED.
  
 4- ACCORDING TO SITE PLAN SUBMITTED, IT LOOKS LIKE THE
 PROPOSED STAIRS ARE OUTSIDE THE PROPERTY LINE OF THIS
 BUILDING. SEE ZONING REVIEW COMMENTS ALSO. REVISE AS
 REQUIRED. PROVIDE COPY OF SURVEY. SEC.107.2.1 CITY
 AMENDMENTS.
  
 5- PERMIT APPLICATION STATES "ADA COMPLIANCE STAIRS AND
 METAL RAILING". PLANS SUBMITTED SHOW WOOD STAIRS AND
 DECK. CLARIFY/REVISE TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 6- A)STAIR DETAILS ARE MISSING THE HANDRAIL AND
 GUARDRAIL COMPLETE DETAILS AND SPECIFICATIONS. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS. SPECIFY ALL
 FRAMING MEMBERS AND CONNECTIONS AS REQUIRED TO RESIST
 THE LIVE LOADS. ALSO, THE TREAD DIMENSION (1'-0") IS
 INCORRECT THE WAY IS SHOWN. 2X12 P.T WOOD TREADS DON'T
 PROVIDE 12". COMPLETE DETAILS AND SPECIFICATIONS WILL
 BE REVIEW ONCE ITEMS #1 AND #2 ABOVE ARE CLARIFIED.
 NOTE: SPECIFY THE LIVE LOADS FOR STAIRS ALSO. SEC.
 107.2.1 CITY AMENDMENTS.
  
 B) STAIR DETAILS ARE MISSING THE LANDING FRAMING
 INFORMATION. SEC. 107.2.1 CITY AMENDMENTS.
  
 C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ALL
 STRINGERS CONNECTIONS. SEC. 107.2.1 CITY AMENDMENTS.
  
 ****ARCHITECT OF RECORD TO PROVIDE RESPONSE LETTER
 ADDRESSING EACH COMMENT TO HELP EXPEDITE THE REVIEW
 PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
2018-10-17 17:46:36 
  
 *****REVIEW IN PROGRESS........