2019-07-22 09:04:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3 (NOT PROVIDED.)
 6. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10 (NOT PROVIDED.)
 7. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. THIS IS NOT IDENTIFIED ON
 PLAN. PROVIDE CORRECTION. NEC 410.10(D); FBC RE
 E4003.11 (NOT CORRECTED.)
 8. CORRECTED.
 9. CORRECTED.
 10. IF THIS IS A NEW PANEL AND SERVICE AS THE PLAN
 SEEMS TO INDICATE, THEN PROVIDE AVAILABLE SHORT CIRCUIT
 CALCULATION FOR SERVICE INCLUDING INFORMATION FROM THE
 POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS FOR THE SERVICE. INDICATE ON PLAN THE AIC
 RATING OF THE SERVICE EQUIPMENT TO CONFIRM IT IS
 ADEQUATE. NEC 110.9, 110.10; FBC RE E3606.3 (NOT
 PROVIDED OR ADDRESSED.)
 11. 4 TIMES FEE ADDED FOR PLAN REVIEW. THIS WILL BE
 ADJUSTED TO MATCH CORRECT CONTRACT VALUE WHEN CONTRACT
 IS SUPPLIED.
 12. RISER DIAGRAM SHOWS THREE # 2 COPPER CONDUCTORS TO
 INTERIOR PANEL. THIS CONDUIT MUST CONTAIN AN EQUIPMENT
 GROUNDING CONDUCOTR, SIZED PER CODE. PROVIDE
 CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1 (NOT
 CORRECTED.)
 13. BATH 1 AND BATH 2 SHOW A 15 AMP CIRCUIT FOR THE
 BATHROOM INCLUDING THE RECEPTACLE OUTLETS. A MINIMUM OF
 ONE 20 AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO
 SUPPLY BATHROOM RECEPTACLE OUTLET(S). PROVIDE
 CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4 (NOT
 CORRECTED.)
 14. DINING ROOM RECEPTACLE OUTLETS ARE REQUIRED TO BE
 ON A 20 AMP CIRCUIT. PROVIDE CORRECTION. NEC
 210.52(B)(2); FBC RE E3703.2 (NOT CORRECTED.)
  
 NEW COMMENT:
  
 15. PER FAC 61G15-23.001 SIGNATURE, DATE AND SEAL SHALL
 BE AFFIXED. A PROFESSIONAL ENGINEER SHALL SIGN, DATE
 AND SEAL ALL FINAL PLANS, PRINTS, SPECIFICATIONS,
 REPORTS, OR OTHER DOCUMENTS PREPARED OR ISSUED BY THE
 LICENSEE AND BEING FILED FOR PUBLIC RECORD. THE DATE IS
 MISSING FROM THE ELECTRICAL PLAN. PROVIDE CORRECTION.
 WPB FBC 107.1; FAC 61G15-23.001
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  