| 2019-05-17 09:55:26 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCC = WEST PALM BEACH CROSS CONNECTION CONTROL |
| | MANUAL |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 3RD REVIEW: |
| | PLUMBING COMMENTS: DENIED! IT DOES NOT APPEAR THAT ANY |
| | OF THE PLUMBING COMMENTS WERE ADDRESSED. I SUGGEST A |
| | MEETING IN ORDER TO EXPEDITE APPROVAL OF THIS PERMIT, |
| | PLEASE CONTACT ME TO SET UP A TIME SEE CONTACT INFO |
| | BELOW. |
| | |
| | 1. P-1 SANITARY RISER DIAGRAM |
| | A. PER WPB FBC 107.2.1, IDENTIFY THE TWO BATHROOM |
| | FIXTURES DOWNSTREAM OF BATHROOM SINK (LAVATORY) AND |
| | IDENTIFY BATHROOM SINK AS LAVATORY. |
| | B. PER WPB FBC 107.2.1, SIZE WATER CLOSET FIXTURE DRAIN |
| | AND REPLACE P-TRAP WITH A VERTICAL TO HORIZONTAL |
| | DISCHARGE PIPE. |
| | C. PER FBC RES P3108.1, KITCHEN SINK SHALL NOT CONNECT |
| | TO THE BATHROOM GROUP. |
| | D. PER FBC RES P3101.2, CLOTHES WASHER FIXTURE DRAIN |
| | SHALL BE VENTED. |
| | E. THE T&P DISCHARGE FROM THE WATER HEATER SHALL COMPLY |
| | WITH THE REQUIREMENTS OF FBC RES P2804.6.1 WHICH |
| | INCLUDES BUT IS NOT LIMITED TO DISCHARGING THROUGH AN |
| | AIR GAP IN THE SAME ROOM. |
| | 2.P-1 WATER RISER DIAGRAM |
| | A. PER FBC RES P2903.5, PROVIDE WATER HAMMER ARRESTORS |
| | FOR CLOTHES WASHER. |
| | 3. WATER HEATER INSTALLATION SHALL COMPLY WITH |
| | REQUIREMENTS OF FBC RES P2108.1 AND P2804 |
| | 4. IS CLOTHES WASHER OUTSIDE? PER WPB FBC 107.2.1, SHOW |
| | THAT IT IS PROTECTED FROM THE ELEMENTS OR PROVIDE |
| | DOCUMENTATION THAT IT IS SUITABLE FOR OUTDOOR USE. |
| | |
| | END OF COMMENTS |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, AA TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |