| 2019-05-29 10:37:16 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL |
| | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND |
| | POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH |
| | AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| | 210.8, 210.12; FBC RE E3902 (NOT PROVIDED.) |
| | 2. CORRECTED. |
| | 3. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| | 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, |
| | E3609.3; WPB FBC 107.2.1 (NOT PROVIDED.) |
| | 4. PROVIDE LOCATION OF METER AND MAIN. (NOT PROVIDED.) |
| | 5. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC |
| | 109.3 (NOT PROVIDED.) |
| | |
| | NEW COMMENTS: |
| | |
| | 6. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| | 210.8(D); FBC RE E3902.10 |
| | 7. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE |
| | SUITABLE FOR DAMP LOCATIONS. THIS IS NOT IDENTIFIED ON |
| | PLAN. PROVIDE CORRECTION. NEC 410.10(D); FBC RE |
| | E4003.11 |
| | 8. PROVIDE COMPLIANCE WITH FBC RE R314.3.1. |
| | 9. LOAD CALCULATION STATES THAT A 125 AMP SERVICE WILL |
| | BE INSTALLED. THE PANEL SCHEDULE SHOWS A PANEL RATED |
| | FOR 100 AMPS. PROVIDE CORRECTION. NEC 408.30, 408.36; |
| | FBC RE E3706.3 |
| | 10. IF THIS IS A NEW PANEL AND SERVICE AS THE PLAN |
| | SEEMS TO INDICATE, THEN PROVIDE AVAILABLE SHORT CIRCUIT |
| | CALCULATION FOR SERVICE INCLUDING INFORMATION FROM THE |
| | POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT |
| | CURRENT IS FOR THE SERVICE. INDICATE ON PLAN THE AIC |
| | RATING OF THE SERVICE EQUIPMENT TO CONFIRM IT IS |
| | ADEQUATE. NEC 110.9, 110.10; FBC RE E3606.3 |
| | 11. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE |
| | NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE NEXT |
| | REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN |
| | AGAIN FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW |
| | IS REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO |
| | EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A |
| | LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO |
| | ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND |
| | ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY |
| | THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A |
| | CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN |
| | EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, |
| | FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B) |
| | THE ADDITIONAL FEE FOR THIS PROJECT WOULD BE $440.00, |
| | BASED ON CURRENT VALUE OF PROJECT. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD |
| | SHEETS?. |
| | |