2018-09-24 15:23:21THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
  
 1) THERE INSUFFICIENT INFORMATION PROVIDED TO DETERMINE
 IF THIS DOOR IS REQUIRED TO BE RATED OR NOT.
  
 IF THIS DOOR IS A CORRIDOR DOOR, IT IMAY REQUIRED TO BE
 RATED PER THE ORIGINAL EOR LIFE SAFETY SYSTEM.
  
 PER NFPA 101,
  
 11.8 HIGH-RISE BUILDINGS.
 11.8.1 GENERAL.
 11.8.1.1 THE PROVISIONS OF SECTION 11.8 SHALL APPLY TO
 THE
 FOLLOWING:
 (1) NEW HIGH-RISE BUILDINGS, AS DEFINED IN 3.3.36.7
 (2) EXISTING HIGH-RISE BUILDINGS AS REQUIRED BY
 CHAPTERS 13, 15,
 17, 19, 21, 23, 26, 29, 31, 33, 37, 39, 40, 42, OR 43
  
 PER THE APPLICABLE CHAPTER THE CORRIDAOR IS REQUIRED TO
 BE RATED.
  
 PLEASE REVIEW ANC CORRECT OR PROVIDE A DETAIL
 JUSTIFICATION WITH SPECIFIC CODE REFERENCES AND OR
 APPLICABLE BUILDING RECORDS.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  