| 2019-02-19 13:32:49 | APPROVED |
| | PROVISO |
| | 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S |
| | APPROVAL |
| | 2. DRINKING FOUNTAIN AND MOP SINK WASTE SHALL CONNECT |
| | DOWNSTREAM OF BATHROOM WET VENT PER FBC 912.1. SEE |
| | REDLINED COMMENTS ON PLAN SHEET A.06 FOR CLARIFICATION. |
| | 3. A THERMAL EXPANSION CONTROL DEVICE IS REQUIRED ON |
| | THE COLD WATER SUPPLY TO THE WATER HEATER IN ACCORDANCE |
| | WITH REQUIREMENTS OF FBC PL 607.3. PER WPB FBC 107.2.1, |
| | SUBMIT IN ACCORDANCE WITH WPB FBC 107.3.4.1 ? DEFERRED |
| | SUBMITTALS?, THE MANUFACTURER?S SPECIFICATIONS FOR THE |
| | THERMAL EXPANSION DEVICE AND PROVIDE SIZE OF SAME. SAID |
| | SUBMITTALS SHALL BE SUBMITTED, APPROVED AND ON THE |
| | JOBSITE PRIOR TO FINAL PLUMBING INSPECTION. |
| | 4. WATER HEATER SHALL BE PROVIDED WITH ANTI-SIPHON |
| | DEVICE FOR COLD WATER SUPPLY PER FBC PL 504.1 AND/OR |
| | 504.2; PROVIDE A RELIEF VALVE IN ACCORDANCE WITH FBC PL |
| | 504.4. |
| | 5. WATER HEATER RELIEF VALVE DISCHARGE PIPING SHALL BE |
| | IN ACCORDANCE WITH THE REQUIREMENTS OF FBC PL 504.6. |
| | 6. WATER HEATER PAN AND DRAIN SHALL BE IN ACCORDANCE |
| | WITH FBC PL 504.7, 507.7.1 AND 507.7.2. |
| | 7. PROVIDE VACUUM BREAKER (S) FOR WATER OUTLETS AT THE |
| | MOP SINK PER FBC PL 608.2. |
| | 8. COMPLY WITH FBC EC C404.3 REGARDING HEAT TRAPS FOR |
| | THE WATER HEATER. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |