| 2018-11-30 04:42:22 | 1) THE LEVEL OF ALTERATION FOR THIS PROJECT SHALL BE |
| | INDICATED ON SHT. A.01 PER 2017 FBC-EXISTING BUILDING |
| | VOLUME SEC.301.1. |
| | 2) LIST THE OCCUPANT LOAD OF THIS SPACE PER 2017 FBC- |
| | BUILDING SEC. 1004.1 AND TABLE 1004.1.2. |
| | 3) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER |
| | 2017 FBC- PLUMBING TABLE 403.1, 410.3, FBC-ACCESS. |
| | SEC.211.2. DRINKING FOUNTAINS SHALL BE HANDICAPPED |
| | ACCESSIBLE. |
| | 4) SHT. A 0.1 - SHEET INDEX LISTS PLUMBING SHEET A 0.6 |
| | BUT THIS SHEET HAS NOT BEEN INCLUDED IN THE SET OF |
| | PLANS. SUBMIT THE PLUMBING SHEET FOR REVIEW. THE SHEET |
| | SHALL BE ELECTRONICALLY SIGNED AND SEALED. FL. ADMIN. |
| | RULE 61G1-16.005. |
| | 5) TEMPERED WATER IS REQUIRED TO THE NEW LAVATORY IN |
| | THE NEW HANDICAPPED TOILET ROOM PER 2017 FBC-PLUMBING |
| | SEC.416.5. |
| | 6) SHT. A 0.4 - DETAIL #5 - THE CENTERLINE OF THE |
| | LAVATORY SHALL BE LOCATED A MINIMUM OF 15 INCHES FROM |
| | ANY SIDE WALL,PARTITION, VANITY OR OTHER OBSTRUCTION. |
| | WHERE IS THE 9 INCHES SHOWN ON THE DETAIL FRROM AND |
| | WHAT IS THE REASON FOR IT? CLARIY.2017 FBC-PLUMBING |
| | SEC.405.3.1. |
| | 7) SHT. A 0.4 - ADA DETAILS #1 - GRAB BARS T5 & T 6 |
| | SHALL BE MEASURED FROM THE FINISH FLOOR TO THE TOP OF |
| | THE GRIPPING SURFACE PER 2017 FBC-ACCESS. SEC.609.4. |
| | 8) SHOW THE CLEAR FLOOR SPACE FOR THE WATER CLOSET AND |
| | THE LAVATORY ON THE PLAN ON SHT. A 0.4 ON DETAIL #6. |
| | COMPLY WITH 2017 FBC-ACCESS. SEC.604.3 & 604.3.2. |
| | (WATER CLOSET). NO OTHER FIXTURES OR OBSTRUCTIONS SHALL |
| | BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE. |
| | 2017 FBC-ACCESS. SEC.606.2 (LAVATORY). |
| | 9) SHT. A 0.4 - DETAIL # 6 - SHOW THE LENGTH AND WIDTH |
| | DIMENSIONS OF THE HANDICAPPED TOILET ROOM ON THE PLANS. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | 10) SHT. A 0.4 - ADA DETAILS #1 - ITEM T7 (COAT HOOK) - |
| | THE COAT HOOK SHALL BE LOCATED A MAXIMUM OF 48 INCHES |
| | ABOVE THE FINISH FLOOR, NOT 54 INCHES AS SHOWN. 2017 |
| | FBC-ACCESS SEC, 308. |
| | 11) SHT. A 0.6 - ADA DETAILS #2 - THE TOILET PAPER |
| | DISPENSER SHALL BE LOCATED IN ACCORDANCE WITH 2017 |
| | FBC-ACCESS. SECTION 604.7. |
| | 12) HOT WATER PIPING SHALL BE INSULATED IN ACCORDANCE |
| | WITH 2017 FBC-PLUMBING SEC.607.5. |
| | 13) SANITARY AND WATER RISERS ARE REQUIRED FOR REVIEW. |
| | WPB AMEND. TO FBC SEC. 107.3.5.1.3. |
| | 14) SUBMIT A DIMENSION PLAN SHOW THE LENGTHS & WIDTHS |
| | OF ALL NEWLY CONSTRUCTED ROOMS AND AREAS. WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | |