| 2019-05-14 11:38:05 | 05/14/19 REVISED PROVISO FOR CLARIFICATION. (PER |
| | SAMANTHA). |
| | |
| | BUILDING REVIEW APPROVED WITH PROVISO (SUBMIT |
| | INFORMATION PRIOR TO INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS): |
| | 1-REVISE PLANS AND RESUBMIT FOR REVIEW. SHOW ATTIC |
| | ACCESS SIZE/LOCATION IN ALL ROOF AREAS IN THE 1ST & 2ND |
| | FLOOR. |
| | 2-SUBMIT PRODUCT APPROVALS FOR REVIEW: A)WINDOW |
| | MULLIONS AND SPECIFY MULLION SIZE. B)DOORS PRODUCT |
| | APPROVAL FL10765-R6 IS FOR NON-IMPACT DOORS. PROVIDE |
| | SHUTTERS PRODUCT APPROVAL AND COMPLETE INSTALLATION |
| | SCHEDULE. C)POLYGLASS ROOF UNDERLAYMENT FL5259-R28: |
| | CLEARLY MARK WHICH ASSEMBLY L IS GOING TO BE USED. D) |
| | SHUTTERS SHOWN ON EXTERIOR ELEVATIONS AND PROVIDE |
| | COMPLETE INSTALLATION SCHEDULE. E) WATER PROOFING AT |
| | TERRACE. PROVIDE PRODUCT APPROVAL THAT IS DESIGNED TO |
| | RECEIVE MATERIAL SPECIFIED BY THE DESIGNER OF RECORD. |
| | F) DESIGNER OF RECORD TO REVIEW/APPROVE ALL PRODUCT |
| | APPROVALS. |
| | 3-SUBMIT COMPLETE INFORMATION FOR ALUMINUM TRELLIS |
| | UNDER SEPARATE PERMIT PER ARCHITECT'S RESPONSE LETTER. |
| | 4-REVISE PLANS AND RE-SUBMIT FOR REVIEW: ENTRY FOYER |
| | FINISH ELEVATION IN ALL PLANS. PER JOHN MELHORN, THE |
| | ELEVATION WILL BE 9'-0" (NAVD OF 1988) NOT 8'-6". |
| | 5-PER JOHN MELHORN, GARAGE WILL HAVE FLOOD VENTS. |
| | PROVIDE PRODUCT APPROVAL AND REVISE PLANS FOR REVIEW |
| | SHOWING LOCATION. ALSO, POWDER ROOM LOCATED IN THE |
| | GARAGE NEEDS TO BE ELEVATED TO 9'-0". |
| | |