| 2018-10-03 11:47:16 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | |
| | PAGE E-0 |
| | |
| | 1) ARC FAULT NOTE #1 TO INCLUDE KITCHEN AND LAUNDRY |
| | AREAS 201,12 (A), FBC RE3902.16 |
| | |
| | 2)RISER DIAGRAM SHOWS NO GROUNDING AT GYM BUILDING. |
| | 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S) |
| | OR BRANCH CIRCUIT |
| | A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE |
| | ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND |
| | CONNECTED TOGETHER. PROVIDE |
| | DETAILS ON PLAN OF GROUNDING ELECTRODE SYSTEM AND |
| | WIRING. NEC 250.32; FBC RE3607.3 |
| | |
| | 3) LOAD CALCULATION FOR DP USES DEMANDED LOADS FROM |
| | PANEL "A"? |
| | PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. |
| | NEC 220; FBC RE3602.3 |
| | |
| | 4) PANEL "A" ON LOAD CALCULATION SHOWS 39.4 KW OF AC |
| | LOAD BUT USES ONLY 16KW LOAD IN THE CALCULATION? |
| | PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. |
| | NEC 220; FBC RE3602.3 |
| | |
| | 5) PANEL DB USES 41.4KW OF LOAD FOR PANEL "A" WHICH HAS |
| | BEEN DEMANDED DOWN TO 41.4KW |
| | |
| | PAGE E-1 |
| | |
| | 6) NO OUTLETS SHOWN FOR GARAGE DOOR OPENERS? (NOT |
| | REQUIRED) |
| | |
| | 7) ALL AIR HANDLERS IN ATTIC NEED LIGHTING OUTLET |
| | INSTALLED PER 210.70(A)(3) |
| | |
| | 8) GROUNDING AT GYM BUILDING TO BE PER 250.32 BUILDINGS |
| | OR STRUCTURES SUPPLIED BY A FEEDER(S) OR BRANCH CIRCUIT |
| | A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE |
| | ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND |
| | CONNECTED TOGETHER. |
| | PROVIDE DETAILS ON PLAN OF GROUNDING ELECTRODE SYSTEM |
| | AND WIRING. NEC 250.32; FBC RE3607.3 |
| | |
| | 9) DISHWASHER TO BE GFCI PROTECTED PER 210.8(D)< FBC |
| | RE3902.10 |
| | |
| | 10) OUTLET FOR WASHER IN GARAGE NOT SHOWN TO BE GFCI, |
| | 210.8; FBC RE3902.2 |