| 2018-10-09 06:22:29 | 10/09/18 2ND POOL PLUMBING REVIEW**DENIED** WITH |
| | COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE PUMP SHOWN ON THE PLAN IS NOT THE SAME AS |
| | SUBMITTED PER ENGINEERED PLAN, PLEASE CLARIFY. WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | 2. 2ND REQUEST, SUBMIT TWO LEGIBLE COPIES OF THE POOL |
| | PUMP CURVE. IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY |
| | IS SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. |
| | THIS IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM |
| | THE TDH CALCULATIONS. ANSI/APSP/ICC 7 - 2013 SECS. |
| | 4.4.9, 4.4.9.1 |
| | 3. 2ND REQUEST, PLEASE PROVIDE SPEC SHEET FOR HEAT PUMP |
| | POOL HEATERS SHALL HAVE A MINIMUM COP OF 4.0 WHEN |
| | TESTED IN ACCORDANCE WITH AHRI 1160, TABLE 2, STANDARD |
| | RATING CONDITIONS? LOW AIR TEMPERATURE. A TEST REPORT |
| | FROM AN INDEPENDENT LABORATORY IS REQUIRED TO VERIFY |
| | PROCEDURE COMPLIANCE. 2017 FBC-ENERGY? SEC. R 403.10.5 |
| | 4. BACKFLOW PREVENTER REQUIRED PER THE CITY OF WEST |
| | PALM BEACH ORD #2853-95. A PERMIT REQUIRED BY A |
| | LICENSED CONTRACTOR AND MUST BE CERTIFIED BY UTILITIES |
| | PRIOR TO FINAL INSPECTION. A DUAL CHECK VALVE MAY BE |
| | USED IF NO POOL FILL IS INSTALLED AT THE METER AND |
| | INSTALLED BY UTILITIES WHICH DO NOT REQUIRE A PERMIT SO |
| | PLEASE CONTACT CITY OF WPB UTILITIES AT 561-822-2240 |
| | FOR FURTHER DIRECTIONS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6720 |
| | |