Notes
Date Text
2018-09-28 16:42:5109/28/2018 1ST POOL PLUMBING REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAIN, PUMP AND HEAT PUMP. WPB AMENDMENTS TO FBC SEC.
 107.2.1.
  
 2. SUBMIT SPECIFICATIONS FOR THE CARTRIDGE FILTER. WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 3. HEAT PUMP POOL HEATERS SHALL HAVE A MINIMUM COP OF
 4.0 WHEN TESTED IN ACCORDANCE WITH AHRI 1160, TABLE 2,
 STANDARD RATING CONDITIONS ? LOW AIR TEMPERATURE. A
 TEST REPORT FROM AN INDEPENDENT LABORATORY IS REQUIRED
 TO VERIFY PROCEDURE COMPLIANCE. 2017 FBC-ENERGY ? SEC.
 R 403.10.5.
  
 4. SUBMIT TWO LEGIBLE COPIES OF THE POOL PUMP CURVE.
 IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC
 TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS
 NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH
 CALCULATIONS. WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. (USING THE
 MANUFACTURER?S PERFORMANCE CURVE FOR THE EXISTING PUMP,
 FIND THE FLOW THAT CORRESPONDS TO THE TOTAL DYNAMIC
 HEAD. THIS IS THE ACTUAL FLOW AT WHICH THE PUMP IS
 CURRENTLY OPERATING, WHICH MAY OR MAY NOT MEET TURNOVER
 RATE AND WATER VELOCITY REQUIREMENTS. VERIFY THE ACTUAL
 FLOW RATE IS BETWEEN THE MINIMUM FLOW BASED ON THE
 TURNOVER RATE AND THE MAXIMUM FLOW BASED ON THE WATER
 VELOCITY.)
  
 5. THE DYNAMIC HEAD CALCULATIONS FOR THE MAXIMUM SYSTEM
 FLOW DOES NOT SHOW ALL FRICTION LOSS THROUGH ALL
 COMPONENTS, CHLORINATORS, HEATER, ETC., ON THE HAYWARD
 CALCULATOR CHART. ASSUME THE TOTAL FRICTION LOSS WOULD
 INCLUDE THE PIPE, FITTINGS (90-DEGREE FITTINGS, 45'S,
 TEES) AND ALSO VALVES AND FILTER. WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. THE SUCTION OUTLET SAFETY COMPLIANCE THAT THE SYSTEM
 FLOW RATE HAS BEEN DETERMINED BY THE MAXIMUM FLOW FROM
 THE PUMP CURVE. THIS METHOD IS NO LONGER PERMITTED BY
 APSP/ANSI-7 2013 EDITION SEC. 4.4.9. TOTAL DYNAMIC HEAD
 CALCULATIONS ARE REQUIRED.
  
 7. BACKFLOW PREVENTER REQUIRED PER THE CITY OF WEST
 PALM BEACH ORD #2853-95. A PERMIT REQUIRED BY A
 LICENSED CONTRACTOR AND MUST BE CERTIFIED BY UTILITIES
 PRIOR TO FINAL INSPECTION. A DUAL CHECK VALVE MAY BE
 USED IF NO POOL FILL IS INSTALLED AT THE METER AND
 INSTALLED BY UTILITIES WHICH DO NOT REQUIRE A PERMIT SO
 PLEASE CONTACT CITY OF WPB UTILITIES AT 561-822-2240
 FOR FURTHER DIRECTIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  