| Plan Review Notes For Permit 18090722 |
| Permit Number |
18090722 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2019-02-26 12:59:55 | APPROVED | | | ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S | | | APPROVAL | | | PROVISO | | | NOTE: CSST EHD 19 IS ACCEPTABLE FOR UP TO 134,000 BTU | | | IN A 60' LONGEST RUN SYSTEM. (PLANS SAY LONGEST RUN IS | | | 46') EXCEEDING 60' WILL REQUIRE A LARGER DIAMETER CSST. | | | FIELD VERIFY INSTALLETION. SEE ROUTING ON PLAN SHEET | | | S-1. | | | |
|