| Notes |
| Date |
Text |
| 2019-02-14 09:09:16 | 15- STEPHEN WATER P.E. CALCULATIONS SUBMITTED: | | | A) FLAT ROOF RAS 117 CALCULATIONS FOR FLORIDA PRODUCT | | | APPROVAL FL477-R8: | | | (1) ENGINEER NEEDS TO REVISE FASTENER SPACING FOR ROOF | | | ZONE #3. THE FASTENER SPACING CAN NOT BE LESS THAN | | | 4"O.C. SEE RAS 117 SEC. 8.1 AND REVISE AS REQUIRED. | | | | | | (2) NEED ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS | | | REQUIRED BY SEC. 471.025 F.S. WHEN SUBMITTING DOCUMENTS | | | FOR PUBLIC RECORDS. | | | NOTE: THIS IS NOT A DIGITAL SUBMITTAL, COPY OF DIGITAL | | | SUBMITTAL IS NOT ACCEPTABLE. | | | | | | B) ENGINEER CALCULATIONS FOR ROOF TILE UNDERLAYMENT | | | FL11602-R7 NEED ENGINEER'S ORIGINAL SEAL AND SIGNATURE | | | AS REQUIRED BY SEC. 471.025 F.S. WHEN SUBMITTING | | | DOCUMENTS FOR PUBLIC RECORDS. | | | NOTE: THIS IS NOT A DIGITAL SUBMITTAL, COPY OF DIGITAL | | | SUBMITTAL IS NOT ACCEPTABLE. | | | | | | | | | APPROVED PRODUCT APPROVALS: | | | 1- BUILT UP ROOFING FL477-R8 | | | 2- ROOF TILE UNDERLAYMENT FL11602-R7. | | | 3- ROOF TILE ADHESIVE FL6332-R8 | | | 4-ROOF TILE FL17152-R3 |
|