| 2019-02-07 12:46:53 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 2ND REVIEW: DENIED |
| | |
| | COMMENTS |
| | 1.SANITARY PLUMBING ISOMETRIC |
| | A. MASTER BATH; |
| | 1) A VENT IS REQUIRED FOR THE TWO (2) LAVATORIES |
| | (TAGGED NEW SINK) |
| | 2) PROVIDE A DRAIN FOR THE OUTDOOR SHOWER. COMPLY WITH |
| | ALL APPLICABLE PROVISIONS OF FBC RES CHAPTERS 30, 31 |
| | AND 32. |
| | B. LAUNDRY ROOM; |
| | 1) THE LAUNDRY SINK IS S-TRAPPED WHICH IS PROHIBITED |
| | PER FBC RES P3201.5. PROVIDE A VENT IN ACCORDANCE WITH |
| | FBC RES P3105.2. |
| | C. BATHROOM #2; |
| | 1) SHOWER AND WC FIXTURE DRAINS MAY NOT CONNECT |
| | UPSTREAM OF THE VENT. EACH FIXTURE DRAIN MUST |
| | INDEPENDENTLY CONNECT TO THE WET VENT PER FBC RES |
| | P3108.1. |
| | 2) A TRAP IS REQUIRED FOR THE SHOWER PER FBC RES |
| | P2601.1 AND FBC PL 1002.1. |
| | 3) THE FIXTURE DRAIN FOR THE LAVATORY (TAGGED NEW SINK) |
| | SHALL RISE VERTICALLY ABOVE THE FLOOR TO A POINT OF |
| | HORIZONTAL CONNECTION, THEN A VERTICAL CONTINUATION OF |
| | VENT OR FOR AIR ADMITTANCE VALVE. THE P-TRAP OUTLET |
| | SHALL CONNECT TO THE POINT OF HORIZONTAL CONNECTION TO |
| | COMPLY WITH FBC RES P3105.2. |
| | D. KITCHEN; |
| | 1) THE NEW SINK AT THE WINDOW IS NOT PROPERLY VENTED. |
| | THE FIXTURE DRAIN FOR THE NEW SINK SHALL RISE |
| | VERTICALLY ABOVE THE FLOOR TO A POINT OF HORIZONTAL |
| | CONNECTION, THEN A VERTICAL CONTINUATION OF VENT OR FOR |
| | AIR ADMITTANCE VALVE. THE P-TRAP OUTLET SHALL CONNECT |
| | TO THE POINT OF HORIZONTAL CONNECTION TO COMPLY WITH |
| | FBC RES P3105.2. |
| | 2) THE COMBINED DISCHARGE FROM A DISHWASHER AND A ONE- |
| | OR TWO-COMPARTMENT SINK, WITH OR WITHOUT A FOOD-WASTE |
| | DISPOSER, SHALL BE SERVED BY A TRAP OF NOT LESS THAN |
| | 11/2 INCHES (38 MM) IN OUTSIDE DIAMETER. THE DISHWASHER |
| | DISCHARGE PIPE OR TUBING SHALL RISE TO THE UNDERSIDE OF |
| | THE COUNTER AND BE FASTENED OR OTHERWISE HELD IN THAT |
| | POSITION BEFORE CONNECTING TO THE HEAD OF THE |
| | FOOD-WASTE DISPOSER OR TO A WYE FITTING IN THE SINK |
| | TAILPIECE ABOVE THE NEW SINK P-TRAP INLET PER FBC RES |
| | P2717. SHOW DISHWASHER CONNECTION TO VERTICAL LEG OF |
| | TRAP INLET PER WPB FBC 107.2.1. |
| | 3) THE NEW SINK AT THE ISLAND BAR IS NOT PROPERLY |
| | VENTED. THE FIXTURE DRAIN FOR THE NEW SINK SHALL RISE |
| | VERTICALLY ABOVE THE FLOOR TO A POINT OF HORIZONTAL |
| | CONNECTION, THEN A VERTICAL CONTINUATION FOR AIR |
| | ADMITTANCE VALVE. THE P-TRAP OUTLET SHALL CONNECT TO |
| | THE POINT OF HORIZONTAL CONNECTION TO COMPLY WITH FBC |
| | RES P3105.2. |
| | E. GENERAL COMMENTS; |
| | 1) THE WATER CLOSETS IN BATHROOM #2 AND THE CABANA BATH |
| | ARE DRAWN SHOWING INTEGRAL TRAP WHICH IS CONFUSING. |
| | PLEASE DRAW TO MATCH THE WATER CLOSET IN THE MASTER |
| | BATH WHICH REFLECTS THE INDUSTRY STANDARD. |
| | 2) ALL LAVATORIES (TAGGED NEW SINK) SHALL BE PROPERLY |
| | LABELED PER WPB FBC 107.2.1. |
| | 3) VENTS HAVE BEEN SHOWN IN A NUMBER OF LOCATIONS |
| | RISING VERTICALLY FROM THE INLET OF THE FIXTURE TRAP. I |
| | HAVE TRIED TO ADDRESS EACH ONE INDIVIDUALLY, HOWEVER, |
| | PLEASE TAKE CARE TO AVOID THIS AS I MAY NOT HAVE |
| | ADDRESSED THEM ALL. |
| | |
| | END OF COMMENTS |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |