Plan Review Notes
Plan Review Notes For Permit 18090722
Permit Number 18090722
Review Stop G
Sequence Number 2
Notes
Date Text
2019-02-07 11:07:391.USE OF PLASTIC PIPING IN THE BUILDING IS PROHIBITED.
 A. PLASTIC PIPE SHALL BE INSTALLED OUTDOORS UNDERGROUND
 ONLY. PLASTIC PIPE SHALL NOT BE USED WITHIN OR UNDER
 ANY BUILDING OR SLAB PER FBC RES G2415.17.1 AND FBC FG
 404.17.1.
 B. WHERE PLASTIC PIPING IS USED IN ACCORDANCE WITH THE
 CODE, SHOW TRANSITION TO ABOVE GROUND PIPING ANDS
 SPECIFY TYPE OF MATERIAL BEING TRANSITIONED TO PER WPB
 FBC 107.2.1.
 C. CORRECT GAS RISER ISO TO REFLECT THE REQUIRED
 CHANGES AND RECONCILE WITH THE FLOOR PLAN ON PLAN PAGE
 S-1 PER WPB FBC 107.2.1.
 2. SECOND REQUEST; SUBMIT TWO COPIES OF THE
 MANUFACTURER?S SPECIFICATION SHEETS / INSTALLATION
 MANUAL FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS CODE
 SEC. 402.2, AND 301.3 OR 2017 FBC-RES. SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED.
 A. THE INSTALLATION MANUALS FOR ALL GAS APPLIANCES /
 EQUIPMENT SHALL BE ONSITE AT THE TIME OF INSPECTION.
 FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 3. SECOND REQUEST; SUBMIT TWO COPIES OF THE APPLICABLE
 SIZING TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A
 NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH SIZING
 TABLE(S) FROM THE GAS CODE OR OTHER STANDARD THAT WERE
 USED IN THE DESIGN OF THIS GAS SYSTEM PER WPB FBC
 107.2.1. REFER TO THE 2017 FBC-FUEL GAS SECS. 401.4,
 401.8, 402.3, AND TABLES 402.4 (1) THRU 402.4 (37) OR
 2017 FBC-RES. SEC. G2413.3, G2412.8, G2413.1, G2413.2,
 & G2413.3.
 4. SECOND REQUEST; SUBMIT MANUFACTURER?S SPECIFICATIONS
 AND INSTALLATION INSTRUCTIONS FOR THE PRESSURE
 REGULATORS. REGULATORS INSTALLED ON THE EXTERIOR OF THE
 BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION.
 IDENTIFY ON THE SPECIFICATION SHEETS WHICH MODEL
 REGULATOR IS BEING INSTALLED AND THE ORIFICE SIZE TO
 ENSURE THE REGULATOR CAN ACCOMMODATE THE BTU LOAD
 THROUGH THE REGULATOR.2017 FGC SEC.410.1, 2017 FBC-RES.
 SEC. G2421.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715