Plan Review Notes
Plan Review Notes For Permit 18090722
Permit Number 18090722
Review Stop B
Sequence Number 2
Notes
Date Text
2019-02-08 11:02:37RESIDENTIAL (R3) ALTERATION/ADDITION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
 1- OK
  
 ORIGINAL COMMENT:
 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 RESPONSE:
 PARTIALLY DONE. NEED TO SHOW DRAINAGE ON THE WEST SIDE
 OF THE ADDITION.
  
 ORIGINAL COMMENT:
 3- SURVEY : FLOOD ZONE INFORMATION SEEMS TO BE
 INCORRECT. ACCORDING TO FEMA MAPS EFFECTIVE 10/05/17
 THE TWO BUILDINGS IN THIS PROPERTY ARE LOCATED IN FLOOD
 ZONE X500 NOT AE. NONE OF THE BUILDINGS (INCLUDING THE
 PROPOSED ADDITION) ARE TOUCHED BY THE FLOOD BOUNDARY
 LINE BETWEEN FLOOD ZONE AE AND ZONE X500. IN ADDITION,
 THE BASE FLOOD ELEVATION IN FLOOD ZONE AE ADJACENT TO
 THIS PROPERTY IS 6 NOT 8. REVISE AS REQUIRED. CLEARLY
 IDENTIFY FLOOD ZONE AREAS IN SURVEY PROVIDED USING THE
 MAPS EFFECTIVE 10/05/17. SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 PARTIALLY DONE. SURVEY WAS REVISED BUT IS NOT SHOWING
 BOTH FLOOD ZONES LOCATED IN THIS PROPERTY.
 ARCHITECTURAL DRAWING SP1 CLEARLY IDENTIFIES BOTH FLOOD
 ZONES. THIS WAY PROPERTY OWNER KNOWS THAT EVEN IF THE
 BUILDINGS ARE NOT CONSIDERED SPECIAL FLOOD HAZARD, THE
 SITE IS NEXT TO AN SPECIAL FLOOD HAZARD ZONE.
  
 4- SHEET S-4:
 A) OK.
  
 B)OK
  
 ORIGINAL COMMENT:
 C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 VENTILATION AND ACCESS AT NEW CRAWL SPACE AS REQUIRED
 BY SEC. R408 FBC-RESIDENTIAL.
  
 RESPONSE:
 PARTIALLY DONE. PLANS DON'T SHOW ACCESS. SEC. R408.4.
  
 D) OK.
  
 5- OK.
  
 6- OK
  
 7- OK.
  
 8- OK.
  
 9- OK.
  
 10- OK
  
 11- OK.
  
 12- OK
  
 B) OK.
  
 C) OK.
  
 D)
  
 13- OK.
  
 14- OK.
  
 15- STEPHEN WATER P.E. CALCULATIONS SUBMITTED:
 A) FLAT ROOF RAS 117 CALCULATIONS FOR FLORIDA PRODUCT
 APPROVAL FL477-R8:
 (1) ENGINEER NEEDS TO REVISE FASTENER SPACING FOR ROOF
 ZONE #3. THE FASTENER SPACING CAN NOT BE LESS THAN
 4"O.C. SEE RAS 117 SEC. 8.1 AND REVISE AS REQUIRED.
  
 (2) NEED ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS
 REQUIRED BY SEC. 471.025 F.S. WHEN SUBMITTING DOCUMENTS
 FOR PUBLIC RECORDS.
 NOTE: THIS IS NOT A DIGITAL SUBMITTAL, COPY OF DIGITAL
 SUBMITTAL IS NOT ACCEPTABLE.
  
 B) ENGINEER CALCULATIONS FOR ROOF TILE UNDERLAYMENT
 FL11602-R7 NEED ENGINEER'S ORIGINAL SEAL AND SIGNATURE
 AS REQUIRED BY SEC. 471.025 F.S. WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
 NOTE: THIS IS NOT A DIGITAL SUBMITTAL, COPY OF DIGITAL
 SUBMITTAL IS NOT ACCEPTABLE.
  
 16- NEW COMMENT: PROVIDE COMPLETE SHUTTERS INSTALLATION
 SCHEDULE FOR PROPOSED SHUTTERS ON EXISTING ENTRY DOORS.
 SEE CITY SAMPLE. SEC. 107.2.1 CITY AMENDMENTS.,
  
 17- OK
  
 18- OK.
  
 19- OK.
  
 20- OK
  
 21-OK
  
 22- OK.
  
 23- OK.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  
  
  