| 2019-02-08 11:02:37 | RESIDENTIAL (R3) ALTERATION/ADDITION SECOND BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| | TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| | OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| | ISSUANCE. |
| | |
| | |
| | 1- OK |
| | |
| | ORIGINAL COMMENT: |
| | 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| | FOLLOWING: |
| | FBC R 401.3 (DRAINAGE) |
| | FBC 107.2.5 (SITE PLAN) |
| | FBC 110.9 (IMPACT OF CONSTRUCTION) |
| | |
| | RESPONSE: |
| | PARTIALLY DONE. NEED TO SHOW DRAINAGE ON THE WEST SIDE |
| | OF THE ADDITION. |
| | |
| | ORIGINAL COMMENT: |
| | 3- SURVEY : FLOOD ZONE INFORMATION SEEMS TO BE |
| | INCORRECT. ACCORDING TO FEMA MAPS EFFECTIVE 10/05/17 |
| | THE TWO BUILDINGS IN THIS PROPERTY ARE LOCATED IN FLOOD |
| | ZONE X500 NOT AE. NONE OF THE BUILDINGS (INCLUDING THE |
| | PROPOSED ADDITION) ARE TOUCHED BY THE FLOOD BOUNDARY |
| | LINE BETWEEN FLOOD ZONE AE AND ZONE X500. IN ADDITION, |
| | THE BASE FLOOD ELEVATION IN FLOOD ZONE AE ADJACENT TO |
| | THIS PROPERTY IS 6 NOT 8. REVISE AS REQUIRED. CLEARLY |
| | IDENTIFY FLOOD ZONE AREAS IN SURVEY PROVIDED USING THE |
| | MAPS EFFECTIVE 10/05/17. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | PARTIALLY DONE. SURVEY WAS REVISED BUT IS NOT SHOWING |
| | BOTH FLOOD ZONES LOCATED IN THIS PROPERTY. |
| | ARCHITECTURAL DRAWING SP1 CLEARLY IDENTIFIES BOTH FLOOD |
| | ZONES. THIS WAY PROPERTY OWNER KNOWS THAT EVEN IF THE |
| | BUILDINGS ARE NOT CONSIDERED SPECIAL FLOOD HAZARD, THE |
| | SITE IS NEXT TO AN SPECIAL FLOOD HAZARD ZONE. |
| | |
| | 4- SHEET S-4: |
| | A) OK. |
| | |
| | B)OK |
| | |
| | ORIGINAL COMMENT: |
| | C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | VENTILATION AND ACCESS AT NEW CRAWL SPACE AS REQUIRED |
| | BY SEC. R408 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | PARTIALLY DONE. PLANS DON'T SHOW ACCESS. SEC. R408.4. |
| | |
| | D) OK. |
| | |
| | 5- OK. |
| | |
| | 6- OK |
| | |
| | 7- OK. |
| | |
| | 8- OK. |
| | |
| | 9- OK. |
| | |
| | 10- OK |
| | |
| | 11- OK. |
| | |
| | 12- OK |
| | |
| | B) OK. |
| | |
| | C) OK. |
| | |
| | D) |
| | |
| | 13- OK. |
| | |
| | 14- OK. |
| | |
| | 15- STEPHEN WATER P.E. CALCULATIONS SUBMITTED: |
| | A) FLAT ROOF RAS 117 CALCULATIONS FOR FLORIDA PRODUCT |
| | APPROVAL FL477-R8: |
| | (1) ENGINEER NEEDS TO REVISE FASTENER SPACING FOR ROOF |
| | ZONE #3. THE FASTENER SPACING CAN NOT BE LESS THAN |
| | 4"O.C. SEE RAS 117 SEC. 8.1 AND REVISE AS REQUIRED. |
| | |
| | (2) NEED ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS |
| | REQUIRED BY SEC. 471.025 F.S. WHEN SUBMITTING DOCUMENTS |
| | FOR PUBLIC RECORDS. |
| | NOTE: THIS IS NOT A DIGITAL SUBMITTAL, COPY OF DIGITAL |
| | SUBMITTAL IS NOT ACCEPTABLE. |
| | |
| | B) ENGINEER CALCULATIONS FOR ROOF TILE UNDERLAYMENT |
| | FL11602-R7 NEED ENGINEER'S ORIGINAL SEAL AND SIGNATURE |
| | AS REQUIRED BY SEC. 471.025 F.S. WHEN SUBMITTING |
| | DOCUMENTS FOR PUBLIC RECORDS. |
| | NOTE: THIS IS NOT A DIGITAL SUBMITTAL, COPY OF DIGITAL |
| | SUBMITTAL IS NOT ACCEPTABLE. |
| | |
| | 16- NEW COMMENT: PROVIDE COMPLETE SHUTTERS INSTALLATION |
| | SCHEDULE FOR PROPOSED SHUTTERS ON EXISTING ENTRY DOORS. |
| | SEE CITY SAMPLE. SEC. 107.2.1 CITY AMENDMENTS., |
| | |
| | 17- OK |
| | |
| | 18- OK. |
| | |
| | 19- OK. |
| | |
| | 20- OK |
| | |
| | 21-OK |
| | |
| | 22- OK. |
| | |
| | 23- OK. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |
| | |
| | |
| | |