Plan Review Notes
Plan Review Notes For Permit 18090722
Permit Number 18090722
Review Stop R
Sequence Number 1
Notes
Date Text
2018-11-07 17:03:431- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) WATER PROOFING AT TERRACE. PROVIDE PRODUCT APPROVAL
 THAT IS DESIGNED TO RECEIVE MATERIAL SPECIFIED BY THE
 DESIGNER OF RECORD. NOTE: COORDINATE WITH ITEM #12(D)
 ABOVE.
 AND, CLEARLY MARK WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE: IF THE
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR
 ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117
 CALCULATIONS ARE REQUIRED.
  
 B) FLAT ROOF FLORIDA PRODUCT APPROVAL FL477-R8
 SUBMITTED: SELECTED ASSEMBLY W-20 ON PAGE 7 OF 23
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES.
 PROVIDE SINGED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY NOTE #9 ON PAGE 2 OF 23 OF PRODUCT APPROVAL
 SUBMITTED. SEC. R301.1 FBC-RESIDENTIAL.
  
 C) ROOFING UNDERLAYMENT FL11602-R5: THE CLAY IS GOING
 TO BE INSTALLED WITH FOAM-ON TILE ADHESIVE. THE MAXIMUM
 DESIGN PRESSURES SHOWN ON SEC. 5.6.3 OF PRODUCT
 APPROVAL SUBMITTED DON'T MEET THE DESIGN PRESSURES FOR
 ALL ROOF ZONES. PROVIDE COMPLETE INFORMATION FROM
 FRSA/TRI SHOWING HOW THE CLAY TILES ARE GOING TO BE
 INSTALLED TO RESIST THE CALCULATED DESIGN PRESSURES.
 NOTE: ACCORDING TO ENGINEER OF RECORD THIS BUILDING IS
 LOCATED IN EXPOSURE D.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  