| Plan Review Notes For Permit 18090722 |
| Permit Number |
18090722 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-10-16 14:37:32 | 1) SHT. S-9 - 2ND FLOOR SANITARY RISER - THE MAXIMUM | | | NUMBER OF FIXTURE UNITS PERMITTED ON A 3 INCH WET VENT | | | SHALL COMPLY WITH 2017 FBC-RES. TABLE P3108.3. | | | 2) THE SINKS ON THE SANITARY RISER ARE NOT VENTED ( | | | EXCEPT THE FIRST FLOOR ISLAND SINK WITH THE AIR | | | ADMITTANCE VALVE). 2017 FBC-RES. SEC. P3101.2.1. | | | 3) CLEANOUTS ARE REQUIRED IN THE WASHING MACINE STACK | | | AND THE STACK FROM THE FIRST FLOOR. | | | 4) THE WAY THE WATER CLOSETS ARE DRAWN ON THE ISOMETRIC | | | IS CONFUSING AND DOES NOT MEET CODE. CLARIFY. | | | 5) SUBMIT A REVISED CODE COMPLIANT SANITARY RISER. | | | THERE ARE JUST TOO MANY CODE VIOLATIONS TO LIST. FBC | | | SEC. 107.2.1, 107.3.5.3. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|