| 2018-10-16 11:24:44 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. E-1 THE SANITARY ISOMETRIC HAS THE FOLLOWING |
| | CODE VIOLATIONS PLEASE CORRECT AND RESUBMIT. |
| | A) THE TOILET ON THE FIRST FLOOR IS NOT VENTED THE |
| | TOILET, SHOWER AND LAVATORY SHOULD CONNECT TO A SINGLE |
| | BUILDING BRANCH DRAIN VENTED BY THE LAVATORY AS A WET |
| | VENT SYSTEM. PER FBC RES P3801.1 |
| | B) THE LAUNDRY IS SHOWN ON THE END OF THE BUILDING |
| | DRAIN THE PLAN SHOWS IT IN THE MIDDLE OF THE BUILDING |
| | IT SHOULD BE SHOWN NEXT TO THE BATHROOM AND THE KITCHEN |
| | SHOWN ON THE END PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | C) THERE SHALL BE A MIN OF 21" CLEARANCE BETWEEN THE |
| | TOILET AND LAVATORY OR VANITY. PER FBC RES P2705.1 (5) |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |