Plan Review Notes
Plan Review Notes For Permit 18090702
Permit Number 18090702
Review Stop P
Sequence Number 1
Notes
Date Text
2018-10-16 11:24:441ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. E-1 THE SANITARY ISOMETRIC HAS THE FOLLOWING
 CODE VIOLATIONS PLEASE CORRECT AND RESUBMIT.
 A) THE TOILET ON THE FIRST FLOOR IS NOT VENTED THE
 TOILET, SHOWER AND LAVATORY SHOULD CONNECT TO A SINGLE
 BUILDING BRANCH DRAIN VENTED BY THE LAVATORY AS A WET
 VENT SYSTEM. PER FBC RES P3801.1
 B) THE LAUNDRY IS SHOWN ON THE END OF THE BUILDING
 DRAIN THE PLAN SHOWS IT IN THE MIDDLE OF THE BUILDING
 IT SHOULD BE SHOWN NEXT TO THE BATHROOM AND THE KITCHEN
 SHOWN ON THE END PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
 C) THERE SHALL BE A MIN OF 21" CLEARANCE BETWEEN THE
 TOILET AND LAVATORY OR VANITY. PER FBC RES P2705.1 (5)
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  