| Date |
Text |
| 2019-04-30 15:02:01 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 1) NEED TO SHOW LOCATION OF SERVICE EQUIPMENT ON LAND |
| | VERSES WATER, AND THEN INCORPORATE THE REQUIREMENTS OF |
| | THE FOLLOWING CODE SECTIONS INTO THE DRAWINGS. |
| | |
| | PLEASE READ THE FOLLOWING NEC CODE SECTIONS THAT |
| | REGULATE THE INSTALLATION OF THIS TYPE OF EQUIPMENT. |
| | |
| | 682. 10 ELECTRICAL EQUIPMENT AND TRANSFORMERS |
| | ELECTRICAL EQUIPMENT AND TRANSFORMERS, INCLUDING THEIR |
| | ENCLOSURES, |
| | SHALL BE SPECIFICALLY APPROVED FOR THE INTENDED |
| | LOCATION. |
| | NO PORTION OF AN ENCLOSURE FOR ELECTRICAL EQUIPMENT NOT |
| | IDENTIFIED |
| | FOR OPERATION WHILE SUBMERGED SHALL BE LOCATED BELOW |
| | THE |
| | ELECTRICAL DATUM PLANE |
| | |
| | 682. 11 LOCATION OF SERVICE EQUIPMENT |
| | ON LAND, THE SERVICE EQUIPMENT FOR FLOATING STRUCTURES |
| | AND SUBMERSIBLE |
| | ELECTRICAL EQUIPMENT SHALL BE LOCATED NO CLOSER THAN |
| | 1.5 M (5 FT) HORIZONTALLY FROM THE SHORELINE AND LIVE |
| | PARTS SHALL |
| | BE ELEVATED A MINIMUM OF 300 MM (12 IN.) ABOVE THE |
| | ELECTRICAL |
| | DATUM PLANE. SERVICE EQUIPMENT SHALL DISCONNECT WHEN |
| | THE WATER LEVEL REACHES THE HEIGHT OF THE ESTABLISHED |
| | ELECTRICAL |
| | DATUM PLANE. |
| | |
| | 682. 12 ELECTRICAL CONNECTIONS |
| | ALL ELECTRICAL CONNECTIONS NOT INTENDED FOR OPERATION |
| | WHILE SUBMERGED |
| | SHALL BE LOCATED AT LEAST 300 MM (12 IN.) ABOVE THE |
| | DECK |
| | OF A FLOATING OR FIXED STRUCTURE, BUT NOT BELOW THE |
| | ELECTRICAL DATUM |
| | PLANE |
| | |
| | 682. 14 SUBMERSIBLE OR FLOATING EQUIPMENT POWER |
| | CONNECTION(S) |
| | (B) L OCATION. THE DISCONNECTING MEANS SHALL BE READILY |
| | ACCESSIBLE |
| | ON LAND, LOCATED NOT MORE THAN 750 MM (30 IN.) FROM THE |
| | RECEPTACLE IT CONTROLS, AND SHALL BE LOCATED IN THE |
| | SUPPLY CIRCUIT |
| | AHEAD OF THE RECEPTACLE. THE DISCONNECTING MEANS SHALL |
| | BE LOCATED |
| | WITHIN SIGHT OF BUT NOT CLOSER THAN 1.5 M (5 FT) FROM |
| | THE SHORELINE |
| | AND SHALL BE ELEVATED NOT LESS THAN 300 MM (12 IN.) |
| | ABOVE THE |
| | DATUM PLANE |
| | |
| | 682.33 EQUIPOTENTIAL PLANES AND BONDING OF |
| | EQUIPOTENTIAL PLANES |
| | AN EQUIPOTENTIAL PLANE SHALL BE INSTALLED WHERE |
| | REQUIRED IN THIS |
| | SECTION TO MITIGATE STEP AND TOUCH VOLTAGES AT |
| | ELECTRICAL EQUIPMENT. |
| | (A) A REAS REQUIRING EQUIPOTENTIAL PLANES. |
| | EQUIPOTENTIAL |
| | PLANES SHALL BE INSTALLED ADJACENT TO ALL OUTDOOR |
| | SERVICE EQUIPMENT |
| | OR DISCONNECTING MEANS THAT CONTROL EQUIPMENT IN OR ON |
| | WATER, THAT HAVE A METALLIC ENCLOSURE AND CONTROLS |
| | ACCESSIBLE TO |
| | PERSONNEL, AND THAT ARE LIKELY TO BECOME ENERGIZED. THE |
| | EQUIPOTENTIAL |
| | PLANE SHALL ENCOMPASS THE AREA AROUND THE EQUIPMENT AND |
| | SHALL EXTEND FROM THE AREA DIRECTLY BELOW THE EQUIPMENT |
| | OUT NOT |
| | LESS THAN 900 MM (36 IN.) IN ALL DIRECTIONS FROM WHICH |
| | A PERSON |
| | WOULD BE ABLE TO STAND AND COME IN CONTACT WITH THE |
| | EQUIPMENT. |
| | |
| | (B) A REAS NOT REQUIRING EQUIPOTENTIAL PLANES. |
| | EQUIPOTENTIAL |
| | PLANES SHALL NOT BE REQUIRED FOR THE CONTROLLED |
| | EQUIPMENT SUPPLIED |
| | BY THE SERVICE EQUIPMENT OR DISCONNECTING MEANS. ALL |
| | CIRCUITS |
| | RATED NOT MORE THAN 60 AMPERES AT 120 THROUGH 250 |
| | VOLTS, SINGLE |
| | PHASE, SHALL HAVE GFCI PROTECTION. |
| | |
| | 2) PLEASE SIBMIT SIGNED CONTRACTS FOR THE WORK SHOWN, |
| | VALUES ARE TO INCLUDE ALL MATERIALS AND LABOR FOR A |
| | FINFIHED PRODUCT. |
| | |
| | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |