Plan Review Notes
Plan Review Notes For Permit 18090687
Permit Number 18090687
Review Stop E
Sequence Number 1
Notes
Date Text
2018-09-19 13:03:03FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 682. 10 ELECTRICAL EQUIPMENT AND TRANSFORMERS
 ELECTRICAL EQUIPMENT AND TRANSFORMERS, INCLUDING THEIR
 ENCLOSURES,
 SHALL BE SPECIFICALLY APPROVED FOR THE INTENDED
 LOCATION.
 NO PORTION OF AN ENCLOSURE FOR ELECTRICAL EQUIPMENT NOT
 IDENTIFIED
 FOR OPERATION WHILE SUBMERGED SHALL BE LOCATED BELOW
 THE
 ELECTRICAL DATUM PLANE
  
 682. 11 LOCATION OF SERVICE EQUIPMENT
 ON LAND, THE SERVICE EQUIPMENT FOR FLOATING STRUCTURES
 AND SUBMERSIBLE
 ELECTRICAL EQUIPMENT SHALL BE LOCATED NO CLOSER THAN
 1.5 M (5 FT) HORIZONTALLY FROM THE SHORELINE AND LIVE
 PARTS SHALL
 BE ELEVATED A MINIMUM OF 300 MM (12 IN.) ABOVE THE
 ELECTRICAL
 DATUM PLANE. SERVICE EQUIPMENT SHALL DISCONNECT WHEN
 THE WATER LEVEL REACHES THE HEIGHT OF THE ESTABLISHED
 ELECTRICAL
 DATUM PLANE.
  
 682. 12 ELECTRICAL CONNECTIONS
 ALL ELECTRICAL CONNECTIONS NOT INTENDED FOR OPERATION
 WHILE SUBMERGED
 SHALL BE LOCATED AT LEAST 300 MM (12 IN.) ABOVE THE
 DECK
 OF A FLOATING OR FIXED STRUCTURE, BUT NOT BELOW THE
 ELECTRICAL DATUM
 PLANE
  
 682. 14 SUBMERSIBLE OR FLOATING EQUIPMENT POWER
 CONNECTION(S)
 (B) L OCATION. THE DISCONNECTING MEANS SHALL BE READILY
 ACCESSIBLE
 ON LAND, LOCATED NOT MORE THAN 750 MM (30 IN.) FROM THE
 RECEPTACLE IT CONTROLS, AND SHALL BE LOCATED IN THE
 SUPPLY CIRCUIT
 AHEAD OF THE RECEPTACLE. THE DISCONNECTING MEANS SHALL
 BE LOCATED
 WITHIN SIGHT OF BUT NOT CLOSER THAN 1.5 M (5 FT) FROM
 THE SHORELINE
 AND SHALL BE ELEVATED NOT LESS THAN 300 MM (12 IN.)
 ABOVE THE
 DATUM PLANE
  
 682.33 EQUIPOTENTIAL PLANES AND BONDING OF
 EQUIPOTENTIAL PLANES
 AN EQUIPOTENTIAL PLANE SHALL BE INSTALLED WHERE
 REQUIRED IN THIS
 SECTION TO MITIGATE STEP AND TOUCH VOLTAGES AT
 ELECTRICAL EQUIPMENT.
 (A) A REAS REQUIRING EQUIPOTENTIAL PLANES.
 EQUIPOTENTIAL
 PLANES SHALL BE INSTALLED ADJACENT TO ALL OUTDOOR
 SERVICE EQUIPMENT
 OR DISCONNECTING MEANS THAT CONTROL EQUIPMENT IN OR ON
 WATER, THAT HAVE A METALLIC ENCLOSURE AND CONTROLS
 ACCESSIBLE TO
 PERSONNEL, AND THAT ARE LIKELY TO BECOME ENERGIZED. THE
 EQUIPOTENTIAL
 PLANE SHALL ENCOMPASS THE AREA AROUND THE EQUIPMENT AND
 SHALL EXTEND FROM THE AREA DIRECTLY BELOW THE EQUIPMENT
 OUT NOT
 LESS THAN 900 MM (36 IN.) IN ALL DIRECTIONS FROM WHICH
 A PERSON
 WOULD BE ABLE TO STAND AND COME IN CONTACT WITH THE
 EQUIPMENT.
  
 (B) A REAS NOT REQUIRING EQUIPOTENTIAL PLANES.
 EQUIPOTENTIAL
 PLANES SHALL NOT BE REQUIRED FOR THE CONTROLLED
 EQUIPMENT SUPPLIED
 BY THE SERVICE EQUIPMENT OR DISCONNECTING MEANS. ALL
 CIRCUITS
 RATED NOT MORE THAN 60 AMPERES AT 120 THROUGH 250
 VOLTS, SINGLE
 PHASE, SHALL HAVE GFCI PROTECTION.
  
 CUT SHEETS FOR CONTROLLER


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved