| 2019-03-18 08:30:27 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18090633 |
| | REVIEWED: MARCH 18, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1) 311.3 FBC[R] FLOORS AND LANDINGS AT EXTERIOR DOORS. |
| | THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH |
| | EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL BE NOT |
| | LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A |
| | DIMENSION OF NOT LESS THAN 36 INCHES (914 MM) MEASURED |
| | IN THE DIRECTION OF TRAVEL. THE SLOPE AT EXTERIOR |
| | LANDINGS SHALL NOT EXCEED 1/4 UNIT VERTICAL IN 12 UNITS |
| | HORIZONTAL (2 PERCENT). |
| | -PLEASE ADD LANDING OUTLINE AND LANDING DIMENSIONS TO |
| | FLOOR PLAN. |
| | |
| | 2) 602 FBC[R] WOOD WALL CONSTRUCTION. |
| | -PROVIDE CONNECTOR TYPE AND SPACING FOR BASE PLATE TO |
| | FOUNDATION. |
| | -PROVIDE CONNECTOR AND SPACING OF LEDGER BOARD AND WALL |
| | STUDS TO EXISTING STRUCTURE. |
| | |
| | 3) 107.3.4 FBC[AMENDED] PREVIOUS COMMENT WAS TO PROVIDE |
| | PRODUCT APPROVALS. THE RESPONSE WAS TO SEE NOTE 1A, 2 |
| | AND 3. |
| | -NOTE 1A HAS NINE DOORS LISTED WITH THE PRODUCT |
| | APPROVAL NUMBER LISTED. PLEASE SELECT THE ONE TO BE |
| | USED AND PRINT OUT TWO COPIES OF THE PRODUCT APPROVAL. |
| | MAKE SURE IT IS APPROVED FOR FLORIDA BUILDING CODE 6 TH |
| | EDITION 2017. |
| | ALSO, WE NEED TWO COPIES OF THE PRODUCT APPROVAL FOR |
| | THE LAUNDRY ROOM DOOR. |
| | |
| | 3) 602.3(3)TABLE FBC[R] REQUIREMENTS FOR WOOD |
| | STRUCTURAL PANEL WALL SHEATHING USED TO RESIST WIND |
| | PRESSURES. |
| | -PROVIDE SHEATHING NAIL SIZE AND SPACING FROM TABLE |
| | R602.3(3). |
| | |
| | 4) THIS COMMENT IS NOT FROM THE BUILDING CODE. THIS IS |
| | A GENERAL OBSERVATION AND NO RESPONSE IS REQUIRED. |
| | -FROM THE LOOK OF LAUNDRY DOOR AND WATER HEATER |
| | PLACEMENT I DO NOT SEE HOW YOU WOULD GET TWO APPLIANCES |
| | IN THE SPACE. WHEN ONE APPLIANCE IS IN IT BLOCKS THE |
| | DOOR AND MAY HINDER THE NEXT APPLIANCE FROM GETTING |
| | INTO SPACE. MAYBE MOVE WATER HEATER DOWN OR CONSIDER |
| | DOUBLE DOORS. |
| | |
| | 5) 905.2.2 FBC[R] & 905.1.1 FBC[R] FOR ROOF SLOPES FROM |
| | TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) AND |
| | LESS THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL |
| | (4:12), DOUBLE UNDERLAYMENT APPLICATION IS REQUIRED. |
| | -ADD ROOF PITCH TO PLANS AND ADD NOTE FOR DOUBLE |
| | UNDERLAYMENT IS PITCH IS LESS THAN FOUR UNITS VERTICAL |
| | IN 12 UNITS HORIZONTAL (4:12) |
| | |
| | NOTES: |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS. |
| | FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE |
| | REQUIRED. |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |