| 2018-11-08 08:29:41 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18090633 |
| | REVIEWED: NOVEMBER 7, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. [FL. STATUTE 471]DOCUMENTS PREPARED BY AN |
| | ARCHITECT/ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE |
| | TO BE SIGNED, SEALED, DATED ORIGINALS. |
| | PLEASE SIGN AND SEAL A-101 AND A-102(BOTH SETS) |
| | |
| | 2. [FBC AMENDED 107.3.5] PROJECT DATA: |
| | OCCUPANCY = R-3 ? |
| | AREA TABULATIONS = STATE WHAT IS EXISTING UNDER AIR |
| | AND, PROPOSED NEW AMOUNT AND TOTAL THAT WILL NOW BE |
| | UNDER AIR. |
| | [FBC EXISTING 501]STATE THE LEVEL OF ALTERATION FOR |
| | WORK BEING PERFORMED. |
| | STATE CODE EDITION BEING USED FOR ALL TRADES. |
| | WE ARE CURRENTLY USING FLORIDA BUILDING CODE(FBC), 6TH |
| | EDITION (2017) |
| | BASIC WIND SPEED=170 |
| | RISK CATEGORY = II ? |
| | EXPOSURE CATEGORY = B,C OR D ? |
| | BUILDING CLASSIFICATION = ENCLOSED ? |
| | MEAN BLDG. HGT. = 0 FT.-0 IN. ? |
| | WIND SPEED V ULT = 170 ? |
| | WIND SPEED V ASD = 132 ? |
| | INTERNAL PRESSURE COEFFICIENT GCPI = +/-0.18 |
| | |
| | 3. [FBC ENERGY R503.1.1]BUILDING ENVELOPE. BUILDING |
| | ENVELOPE ASSEMBLIES THAT ARE PART OF THE ALTERATION |
| | SHALL COMPLY WITH SECTION R402.1.2 OR R402.1.4, |
| | SECTIONS R402.2.1 THROUGH R402.2.13, R402.3.1, |
| | R402.3.2, R402.4.3 AND R402.4.5 |
| | |
| | 4. [FBC EXISTING 807.2]NEW STRUCTURAL ELEMENTS. |
| | NEW STRUCTURAL ELEMENTS IN ALTERATIONS, INCLUDING |
| | CONNECTIONS AND ANCHORAGE, SHALL COMPLY WITH THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | PROVIDE IN-FILL DETAIL, DOOR/WINDOW BUCK DETAILS AND |
| | NEW COVERED LAUNDRY AREA CONSTRUCTION DETAILS. |
| | |
| | 5. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVALS FOR |
| | WINDOWS AND DOORS, OR INDICATE THAT YOU WOULD LIKE THEM |
| | DEFERED. |
| | PROVIDE NEW DOOR/WINDOWS DESIGN PRESSURES AND SIZES. |
| | |
| | 6. [FBC AMENDED 107.3.5]IF NEW ROOF OVER THE LAUNDRY |
| | AREA PROVIDE PRODUCT APPROVAL FOR ROOFING MATERIAL TO |
| | BE USED. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |