| 2019-01-16 09:51:15 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18090632 |
| | 1/16/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | NFPA 37-2018 |
| | NFPA 110- |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) REFER TO SECTIONS 7.7.2,1 &, 7.7.2.3 & 7.7.3 NFPA |
| | 110: PER THE ENGINEER'S PLAN AND NARRATIVE, THE |
| | VENTILATION AIR FOR THE GENERATOR IS BEING DRAWN IN |
| | THROUGH A LOUVERED OPENING IN THE 2HR. FIRE-RATED WALL |
| | GENERATOR ROOM WALL THAT ADJACENT TO THE PARKING GARAGE |
| | WHICH IS NOT PERMITTED PER SECTION 7.7.2.1 & 7.7.3. |
| | THESE SECTIONS STATE THAT VENTILATION AIR MUST BE |
| | SUPPLIED DIRECTLY FROM A SOURCE OUTSIDE THE BUILDING. |
| | SECTION 7.7.2.3 PROHIBITS THE USE OF A FIRE DAMPER TO |
| | PROTECT THE OPENING, THEREFORE THE VENTILATION OPENING |
| | LOCATION WOULD NOT BE COMPLIANT BECAUSE OPENINGS IN |
| | FIRE BARRIERS REQUIRE PROTECTION ACCORDING TO SECTION |
| | 607.5.2 FBC M. |
| | |
| | 2) THE SUBMITTED CUT SHEET FOR THE IN LINE FAN (EF-2) |
| | IN THE GENERATOR/TANK ROOM IS FOR A MODEL THAT IS NOT |
| | THE SAME AS FAN IN THE SUBMITTED SCHEDULE. THE NEW FAN |
| | DOES NOT APPEAR TO BE IN COMPLAINCE WITH SECTIONS 503.1 |
| | AND 503.2 FBC M WHICH REQUIRE THE MOTOR FOR THE FAN TO |
| | BE OUTSIDE THE DUCT, AND ALL PARTS OF THE FAN IN |
| | CONTACT WITH FLAMMABLE VAPORS, FUMES, OR DUSTS SHALL BE |
| | OF NONFERROUS OR NONSPARKING MATERIALS ETC. |
| | |
| | 3) THE EXHAUST DUCT WORK FOR EF-2 SHALL BE G90 PER |
| | SECTIONS 510.9 AND SHALL ALSO BE ENCLOSED IN 2HR, |
| | FIRE-RESISTANT RATED CONSTRUCTION FROM POINT OF |
| | PENETRATRION TO THE OUTLET TERMINAL- SECTIONS 510.2 & |
| | 510.7.3 FBC M, AND 6.3.6.5.1 NFPA 37. |
| | |
| | 4) AS PREVIOUSLY REQUESTED SUBMIT THE GENERATOR EXHAUST |
| | PIPE SPECS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |