| Plan Review Notes For Permit 18090632 |
| Permit Number |
18090632 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-09-25 05:47:59 | 1) PROVIDE A COMPLETE DESCRIPTION OF THE WORK ON THE | | | PERMIT APPLICATION. THE DESCRIPTION OF WORK ON THE | | | APPLICATION JUST NOTES "GENERATOR". IS THIS GENERATOR | | | REPLACING AN EXISTING? THE PLANS ARE VAGUE. 2017 FBC | | | SEC. 107.2.1. | | | 2) THE PLANS SHOW A FUEL TANK. IS THE TANK NEW OR | | | ESISTING? WHAT IS THE CAPACITY? WHAT TYPE OF TANK IS | | | IT? SUBMIT 2 COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS FOR THE FUEL TANK. 2017 FBC SEC. | | | 107.2.1. | | | 3) THE TANK INSTALLATION SHALL COMPLY WITH THE | | | APPLICABLE REQUIREMENTS OF NFPA 30. | | | 4) SUBMIT TWO COPIES OF THE MSDS SHEETS FOR THE FUEL. | | | 2017 FBC SEC. 107.2.1. | | | 5) SUBMIT A FUEL PIPING RISER DIAGRAM FOR ANY NEW FUEL | | | PIPING THAT WILL BE INSTALLED. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|