| 2018-10-17 13:00:54 | PER NFPA 110 |
| | |
| | 7.2 LOCATION. |
| | 7.2.1 INDOOR EPS INSTALLATIONS. THE EPS SHALL BE |
| | INSTALLED IN A |
| | SEPARATE ROOM FOR LEVEL 1 INSTALLATIONS. |
| | 7.2.1.1 THE EPS ROOM SHALL BE SEPARATED FROM THE REST |
| | OF THE |
| | BUILDING BY CONSTRUCTION WITH A 2-HOUR FIRE RESISTANCE |
| | RATING. |
| | |
| | PLEASE PROVIDE DETAILS OF THE RATING OF THE PROPOSED |
| | ROOM AND DOOR TO THIS GENERATOR ROOM. |
| | |
| | |
| | |
| | |
| | |
| | THERE IS AN INDICATION OF EXHAUST PIPING, HOWEVER, |
| | THERE ARE NO DETAILS. |
| | |
| | PER NFPA 110 |
| | |
| | 7.10 EXHAUST SYSTEM. |
| | 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION, |
| | INCLUDING |
| | PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN |
| | ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION |
| | AND USE OF |
| | STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND |
| | OTHER APPLICABLE |
| | STANDARDS. |
| | 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO |
| | PREVENT |
| | EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS OR |
| | BUILDINGS |
| | AND TERMINATE IN SUCH A MANNER THAT TOXIC FUMES CANNOT |
| | REENTER A BUILDING OR STRUCTURE, PARTICULARLY THROUGH |
| | WINDOWS, |
| | AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE |
| | SYSTEM. |
| | 7.10.3* EXHAUST PIPING SHALL BE CONNECTED TO THE PRIME |
| | MOVER |
| | BY MEANS OF A FLEXIBLE CONNECTOR AND SHALL BE |
| | INDEPENDENTLY |
| | SUPPORTED THEREAFTER SO THAT NO DAMAGING WEIGHT OR |
| | STRESS IS |
| | APPLIED TO THE ENGINE EXHAUST MANIFOLD OR TURBOCHARGER. |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS AND SPEC SHEETS. |
| | |
| | |
| | |
| | |
| | THERE IS AN INDICATION OF A FUEL TANK INSIDE THE |
| | GENERATOR ROOM. THERE IS NO INDICATIONS IF IT MEETS THE |
| | REQUIREMENTS OF NFPA 110 OR OTHER APPLICABLE CODES. |
| | |
| | PER NFPA 110 |
| | |
| | 7.9.1.1 ALL FUEL TANKS AND SYSTEMS SHALL BE INSTALLED |
| | AND MAINTAINED |
| | IN ACCORDANCE WITH NFPA 30, FLAMMABLE AND COMBUSTIBLE |
| | LIQUIDS CODE; NFPA 37, STANDARD FOR THE INSTALLATION |
| | AND USE OF |
| | STATIONARY COMBUSTION ENGINES AND GAS TURBINES; NFPA |
| | 54, NATIONAL |
| | FUEL GAS CODE; AND NFPA 58, LIQUEFIED PETROLEUM GAS |
| | CODE. |
| | 7.9.3.1* GALVANIZED FUEL LINES SHALL NOT BE USED. |
| | 7.9.3.2 APPROVED FLEXIBLE FUEL LINES SHALL BE USED |
| | BETWEEN THE |
| | PRIME MOVER AND THE FUEL PIPING. |
| | 7.9.11 ALL MANUAL FUEL SYSTEM VALVES SHALL BE OF THE |
| | INDICATING |
| | TYPE. |
| | 7.9.12.1 A MINIMUM CLEARANCE OF 0.9 M (36 IN.) SHALL BE |
| | MAINTAINED ON ALL SIDES. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | |
| | THERE IS AN INDICATION OF A FUEL TANK WITHIN THE |
| | GENERATOR ROOM. THERE IS NO INDICATION IF THIS TANK IS |
| | DOUBLE WALLED OR THERE IS CONTAIMENT. |
| | |
| | PER NFPA 30 |
| | |
| | 9.13* CONTAINMENT, DRAINAGE, AND SPILL CONTROL. |
| | 9.13.1 STORAGE AREAS SHALL BE DESIGNED AND OPERATED TO |
| | PREVENT |
| | THE DISCHARGE OF LIQUIDS TO PUBLIC WATERWAYS, PUBLIC |
| | SEWERS, |
| | OR ADJOINING PROPERTY, UNLESS SUCH DISCHARGE HAS BEEN |
| | SPECIFICALLY |
| | APPROVED. |