 PLUMBING COMMENTS:
  
 1. SHOW ALL THE PLUMBING FIXTURES ON THE FLOOR PLAN.
 PER WPB AMEND TO FBC 107.2.1
  
 2. THE DISCHARGE PIPING FROM THE PRESSURE AND
 TEMPERATURE VALVE SHALL DISCHARGE THROUGH AN AIR GAP IN
 THE SAME ROOM. FBC PL 504.6(2)3
  
 3. THE LAVATORIES IN THE BATHROOMS SHALL HAVE
 TEMPERATURE LIMITING DEVISE ON HOT SIDE TO LIMIT
 TEMPERATURE OF THE WATER TO TEMPERED WATER THE VALVE
 SHALL COMPLY WITH ASSE 1070 OR CSA B125.3 . PER FBC PL
 416.4
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  