| 2018-09-16 16:53:19 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE |
| | CORRECTION. NEC 210.12; FBC RE E3902.16 |
| | 2. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 |
| | 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, |
| | 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 |
| | 4. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| | 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, |
| | E3609.3; WPB FBC 107.2.1 |
| | 5. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| | PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING |
| | ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS |
| | NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC |
| | 107.2.16. |
| | 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD |
| | SHEETS?. |
| | |