2018-10-25 08:20:22****CORRECTIONS****
 W.P.B. PERMIT: 18090601
 REVIEWED: OCTOBER 24, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC 107.3.5] THIS IS AN ADDITION, NOT A LEVEL 1
 ALTERATION.
  
 2. [FBC 107.2.5]PROVIDE A SURVEY TO SHOW THE LOCATION
 ON SITE WITH SET BACKS AND SEPARATION FROM OTHER
 STRUCTURE.
  
 3. [FBC 107.3.5]
 PROVIDE PROJECT DATA:
 AREA OF EXISTING
 AREA OF NEW ROOM
 TYPE OF CONSTRUCTION FOR EXISTING HOUSE
  
 4. [FBC 107.3.5] THIS ADDITION DOESN?T MEET DEFINITION
 OF A BEDROOM.
 -70 SQ. FT MIN. OF AIR CONDITIONED WITH CLOSET AND
 MEANS OF ESCAPE.
 IT HAS THE 70 SQ. FT., BUT NO CLOSET AND NO MEANS OF
 ESCAPE.
 ADD CLOSET OR CHANGE ROOM DESIGNATION.
 ALSO, PLEASE SHOW DETAILS OF WINDOW-SIZE AND CONNECTION
 DETAILS. WHAT IS THE EXISTING WALL SHOWN MADE FROM? HOW
 DOES THIS WALL MEET WIND RESISTANCE?
 PROVIDE PRODUCT APPROVAL FOR WINDOW, OR INDICATE THAT
 YOU WOULD LIKE TO DEFER THE SUBMITTAL.
 ALSO, HOW IT MEETS OPENING PROTECTION (IMPACT OR
 SHUTTERS). IF SHUTTER SUPPLY THE PRODUCT APPROVAL, OR
 INDICATE THAT YOU WANT TO DEFER THE SUBMITTAL.
  
 5. [FBC R602.2]DETAIL 1 SAYS EXISTING 2X8 @ 16? O.C.
 IT APPEARS THAT ONE WALL IS IN PLACE AND IT IS STATED
 THAT 2 WALLS ARE TO BE CONSTRUCTED.
 PLEASE PROVIDE A WAY FOR ME TO TELL WHAT IS NEW AND
 WHAT IS EXISTING. A DEMO PLAN MAY HELP TO CLARIFY THIS
 BY SHOWING EXISTING ROOF AND POST SUPPORTS.
 [FBC R602.2]PROVIDE DETAIL OF LEDGER CONNECTION TO
 EXISTING STRUCTURE. IF THIS IS EXISTING THEN STATE HOW
 IT IS CONNECTED NOW AND HOW THAT WILL MEET WIND UPLIFT.
  
 6. [FBC R403.1.4]MINIMUM DEPTH.
 EXTERIOR FOOTINGS SHALL BE PLACED NOT LESS THAN 12
 INCHES (305 MM) BELOW THE UNDISTURBED GROUND SURFACE.
 WHERE APPLICABLE, THE DEPTH OF FOOTINGS SHALL ALSO
 CONFORM TO SECTIONS R403.1.4.1 THROUGH R403.1.4.2.
 ALL WALLS WILL NEED FOOTER TO SUPPORT THE DEAD LOADS
 AND THE FOOTER WILL NEET TO RESIST UPLIFT FOR A WOOD
 FRAMED STRUCTURE.
 PROVIDE FLOOR AND ROOF LIVE/DEAD LOADS AND SHOW HOW
 UPLIFT RESISTANCE IS PROVIDED BY THE FOOTER AND AT
 CONNECTORS OF NEW TO EXISTING.
  
 7. [FBC R506.2.3]VAPOR RETARDER.
 A 6-MIL (0.006 INCH; 152 ?M) POLYETHYLENE OR APPROVED
 VAPOR RETARDER WITH JOINTS LAPPED NOT LESS THAN 6
 INCHES (152 MM) SHALL BE PLACED BETWEEN THE CONCRETE
 FLOOR SLAB AND THE BASE COURSE OR THE PREPARED SUBGRADE
 WHERE NO BASE COURSE EXISTS.
  
 8. [FBC R403.1.6]FOUNDATION ANCHORAGE FOR WOOD SILL
 PLATE
  
 9. [FBC R318]INDICATE THE MEANS OF TERMITE PROTECTION
 PROPOSED AND REFERENCE SECTION R308 FOR STANDARDS.
 HOW WILL THE NEW INTERIOR SPACE GET TERMITE PROTECTION
 WITH EXISTING SLAB.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  