| 2019-01-10 09:07:52 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 2ND REVIEW: |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. SECOND REQUEST |
| | A) RE: PLAN SHEET A2, A3, P0.1, P2.1 & P3.1; THE |
| | ACCESSIBILITY CODE REQUIRES A MINIMUM OF 1 SINK IN EACH |
| | TYPE OF ACCESSIBLE ROOM COMPLY WITH FBC ACC 606 PER FBC |
| | ACC 212.3. PLEASE NOTE THAT THE ARCHITECT HAS NOT |
| | PROVIDED THIS INFORMATION ON THE PLANS AND NEEDS TO DO |
| | SO BEFORE THE PLUMBING PERMIT APPLICATION CAN BE |
| | APPROVED. THE PROVIDED INFORMATION BY THE ARCHITECT |
| | NEEDS TO INCLUDE SUCH THINGS AS THE DESIGNATED |
| | ACCESSIBLE ROOM (IE. EXAM RM #4), MILL WORK PLAN AND |
| | ELEVATION VIEWS, AND POSSIBLY ANOTHER DESIGNATED |
| | PLUMBING FIXTURE IN THE PLUMBING FIXTURE SCHEDULE. |
| | 2. PLAN SHEET A2 INDICATES AN EXISTING WATER HEATER IN |
| | THE EXISTING STORAGE ROOM. P0.1 AND P3.1 INDICATE A NEW |
| | WATER HEATER. |
| | A) RESPONSE BY ENGINEER IS THAT THE EXISTING WATER |
| | HEATER IS TO BE REPLACED WITH A NEW WATER HEATER OF |
| | LIKE KIND. REQUIRED INFORMATION CONCERNING THIS HAS |
| | BEEN INCLUDED IN THE PLUMBING FIXTURE SCHEDULE AND |
| | DETAIL. |
| | B) ARCHITECT TO REMOVE NOTE ?EXISTING WATER HEATER? AND |
| | ON PLAN SHEET A2 AND PROVIDE NOTE ?REPLACE EXISTING |
| | WATER HEATER WITH NEW? PER WPB FBC 107.2.1 |
| | 3. RE: PLAN SHEET A1; CODE SUMMARY. REFERENCES TO |
| | FLORIDA ACCESSIBILITY CODE 2014, FBC PLUMBING CODE 2014 |
| | AND FBC FUEL GAS CODE 2014 SHALL BE CORRECTED TO SHOW |
| | COMPLIANCE WITH THE 6TH EDITION, 2017 CODE PER WPB FBC |
| | 107.2.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | |