| 2018-10-30 15:10:05 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW: |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. RE: PLAN SHEET A2, A3, P0.1, P2.1 & P3.1 & P: THE |
| | ACCESSIBILITY CODE REQUIRES A MINIMUM OF 1 SINK IN EACH |
| | TYPE OF ACCESSIBLE ROOM COMPLY WITH FBC ACC 606 PER FBC |
| | ACC 212.3. PLEASE NOTE THAT THE ARCHITECT HAS NOT |
| | PROVIDED THIS INFORMATION ON THE PLANS AND NEEDS TO DO |
| | SO BEFORE THE PLUMBING PERMIT APPLICATION CAN BE |
| | APPROVED. THE PROVIDED INFORMATION BY THE ARCHITECT |
| | NEEDS TO INCLUDE SUCH THINGS AS THE DESIGNATED |
| | ACCESSIBLE ROOM (IE. EXAM RM #4), MILL WORK PLAN AND |
| | ELEVATION VIEWS, AND POSSIBLY ANOTHER DESIGNATED |
| | PLUMBING FIXTURE IN THE PLUMBING FIXTURE SCHEDULE. |
| | 2. PLAN SHEET A2 INDICATES AN EXISTING WATER HEATER IN |
| | THE EXISTING STORAGE ROOM. P0.1 AND P3.1 INDICATE A NEW |
| | WATER HEATER. PLEASE CLARIFY ON PLANS. WPB FBC 107.2.1 |
| | 3. NEW EXAM RMS 17 AND 18 HAVE BEEN REMOVED FROM THE |
| | SCOPE OF WORK. PLEASE REMOVE THE PIPING SHOWN ON P0.1, |
| | P2.1 AND P3.1 THAT SERVICES THESE ROOMS OR INDICATE |
| | NIC.. WPB FBC 107.2.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | |
| | |