| 2018-09-27 14:55:04 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. ANNOTATE ON PLAN THE REQUIRED REDUNDANT GROUNDING |
| | FOR RECEPTACLES AND EQUIPMENT IN PATIENT CARE AREAS. |
| | (EXAM & NST ROOMS). 517.13A&B NEC. |
| | |
| | 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. NEC 220; FBC RE E3602.2 |
| | |
| | 3. RECEPTACLES WITHIN 6' OF SINKS MUST BE GFCI |
| | PROTECTED. SOME RECEPTACLES ON PLAN MARKED SFI??? |
| | 210.8B5 NEC |
| | |
| | 4. OCCUPANCY SENSOR REQUIRED IN DR'S OFFICES FBC EC |
| | C405.2.2.2 |
| | |
| | 5. ENGINEERED DRAWING HAS BEEN MARKED WITH PERMANENT |
| | MARKER SAYING "NO WORK" AND NOT INITIALED BY THE DESIGN |
| | PROFESSIONAL TO INDICATE HE/SHE MADE THE CHANGE. |
| | PROVIDE CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC |
| | 107.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WPB |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |