Plan Review Notes
Plan Review Notes For Permit 18090587
Permit Number 18090587
Review Stop E
Sequence Number 1
Notes
Date Text
2018-10-01 15:42:07ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 BASED OFF THE PICTURES PROVIDED FROM PLUMBING INSPECTOR
 LUIS CRESPO WHEN STOP WORK ORDER WAS ISSUED THE SCOPE
 OF WORK STATING "ONLY REPLACING RECEPTACLES, FIXTURES,
 AND PANEL" IS NOT ACCURATE. BRANCH CIRCUIT WIRING WAS
 DONE ALSO.
  
 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC
 107.3.5; FBC RE E3706.2, E3902
  
 ALL RECEPTACLES TO BE TAMPER RESISTANT 406.12 NEC
  
 DINING ROOM:
  
 2. MISSING RECEPTACLE IN DINING ROOM. 210.52A1 NEC
  
 3. NEED EGRESS LIGHT OUTSIDE DINING ROOM DOOR TO
 OUTSIDE. 210.70A2B NEC
  
 4. NEED SMOKE/CARBON MONOXIDE ALARM ON FIRST FLOOR. FBC
 R 314.1 315.1
  
 5. NEED AFCI PROTECTION FOR OUTLETS (RECEPTACLES AND
 LIGHTING) IN DINING ROOM. 210.12A
  
 KITCHEN:
  
 6. NEED RECEPTACLE TO RIGHT OF STOVE 210.52C1
  
 7. ALL COUNTERTOP RECEPTACLES IN KITCHEN MUST BE
 GFCI/AFCI PROTECTED 210.12A, 210.8A6 NEC
  
 8. SHOW FRIDGE RECEPTACLE 210.52B1 NEC MUST BE AFCI
 PROTECED 210.12A NEC
  
 9. LIGHTING IN KITCHEN MUST BE AFCI PROTECTED 210.12A
 NEC
  
 10. DISHWASHER MUST BE BOTH AFCI/GFCI PROTECTED 210.8D,
 210.12A NEC
  
 11. NO EGRESS LIGHT OUTSIDE KITCHEN DOOR. 210.70A2B
  
 LIVING ROOM:
  
 12. WALL RECEPTACLE SPACING INCORRECT IN LIVING ROOM.
 210.52A1 NEC
  
 13. ALL OUTLETS IN LIVING ROOM TO BE AFCI PROTECTED.
 (RECEPTACLES AND LIGHTING) 210.12A
  
 14. NEED SWITCHED RECEPTACLE IN LIVING ROOM. 210.70A1
 NEC
  
 FAMILY ROOM:
  
 15. ALL OUTLETS IN FAMILY ROOM TO BE AFCI PROTECTED.
 (RECEPTACLES AND LIGHTING) 210.12A
  
 16. NEED SWITCHED RECEPTACLE IN FAMILY ROOM. 210.70A1
 NEC
  
 PORCH:
  
 17. PORCH NEEDS EGRESS LIGHT 210.70A2B
  
 18. NEED ATLEAST ONE RECEPTACLE AT FRONT AND REAR OF
 HOME (EXTERIOR) 210.52E1 NEC
  
 BEDROOMS:
  
 19. NEED SWITCHED RECEPTACLE IN ALL BEDROOMS ROOM.
 210.70A1 NEC
  
 20. NEED SMOKE ALARMS IN ALL BEDROOMS. FBC R314.1
  
 21. NEED SMOKE/CARBON MONOXIDE ALARMS OUTSIDE BEDROOMS.
 FBC R 315.1
  
 22. ALL OUTLETS IN BEDROOMS TO BE AFCI PROTECTED.
 (RECEPTACLES AND LIGHTING) 210.12A
  
 HALLWAY:
  
 23. NEED 3-WAY SWITCH AT TOP AND BOTTOM OF STAIRS WITH
 LIGHT FOR STAIRS. 210.70A2 (A&C)
  
 BATHROOM:
  
 24. NO LIGHT SWITCH IN BATHROOM FOR LIGHT. 210.70A1
  
 LAUNDRY ROOM:
  
 25. ALL OUTLETS MUST BE AFCI. 210.12A
  
 26. WASHING MACHINE MUST ME AFCI/GFCI 210.8A10, 210.12A
 NEC
  
 OUTSIDE SERVICE:
  
 27. MINIMUM #4 CU TO COLD WATERPIPE 250.66 NEC
  
 28. NEED SERVICE RECEPTACLE WITHIN 50' OF SERVICE
 EQUIPMENT. 210.64 NEC
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER