| 2018-10-01 15:42:07 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | BASED OFF THE PICTURES PROVIDED FROM PLUMBING INSPECTOR |
| | LUIS CRESPO WHEN STOP WORK ORDER WAS ISSUED THE SCOPE |
| | OF WORK STATING "ONLY REPLACING RECEPTACLES, FIXTURES, |
| | AND PANEL" IS NOT ACCURATE. BRANCH CIRCUIT WIRING WAS |
| | DONE ALSO. |
| | |
| | 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC |
| | 107.3.5; FBC RE E3706.2, E3902 |
| | |
| | ALL RECEPTACLES TO BE TAMPER RESISTANT 406.12 NEC |
| | |
| | DINING ROOM: |
| | |
| | 2. MISSING RECEPTACLE IN DINING ROOM. 210.52A1 NEC |
| | |
| | 3. NEED EGRESS LIGHT OUTSIDE DINING ROOM DOOR TO |
| | OUTSIDE. 210.70A2B NEC |
| | |
| | 4. NEED SMOKE/CARBON MONOXIDE ALARM ON FIRST FLOOR. FBC |
| | R 314.1 315.1 |
| | |
| | 5. NEED AFCI PROTECTION FOR OUTLETS (RECEPTACLES AND |
| | LIGHTING) IN DINING ROOM. 210.12A |
| | |
| | KITCHEN: |
| | |
| | 6. NEED RECEPTACLE TO RIGHT OF STOVE 210.52C1 |
| | |
| | 7. ALL COUNTERTOP RECEPTACLES IN KITCHEN MUST BE |
| | GFCI/AFCI PROTECTED 210.12A, 210.8A6 NEC |
| | |
| | 8. SHOW FRIDGE RECEPTACLE 210.52B1 NEC MUST BE AFCI |
| | PROTECED 210.12A NEC |
| | |
| | 9. LIGHTING IN KITCHEN MUST BE AFCI PROTECTED 210.12A |
| | NEC |
| | |
| | 10. DISHWASHER MUST BE BOTH AFCI/GFCI PROTECTED 210.8D, |
| | 210.12A NEC |
| | |
| | 11. NO EGRESS LIGHT OUTSIDE KITCHEN DOOR. 210.70A2B |
| | |
| | LIVING ROOM: |
| | |
| | 12. WALL RECEPTACLE SPACING INCORRECT IN LIVING ROOM. |
| | 210.52A1 NEC |
| | |
| | 13. ALL OUTLETS IN LIVING ROOM TO BE AFCI PROTECTED. |
| | (RECEPTACLES AND LIGHTING) 210.12A |
| | |
| | 14. NEED SWITCHED RECEPTACLE IN LIVING ROOM. 210.70A1 |
| | NEC |
| | |
| | FAMILY ROOM: |
| | |
| | 15. ALL OUTLETS IN FAMILY ROOM TO BE AFCI PROTECTED. |
| | (RECEPTACLES AND LIGHTING) 210.12A |
| | |
| | 16. NEED SWITCHED RECEPTACLE IN FAMILY ROOM. 210.70A1 |
| | NEC |
| | |
| | PORCH: |
| | |
| | 17. PORCH NEEDS EGRESS LIGHT 210.70A2B |
| | |
| | 18. NEED ATLEAST ONE RECEPTACLE AT FRONT AND REAR OF |
| | HOME (EXTERIOR) 210.52E1 NEC |
| | |
| | BEDROOMS: |
| | |
| | 19. NEED SWITCHED RECEPTACLE IN ALL BEDROOMS ROOM. |
| | 210.70A1 NEC |
| | |
| | 20. NEED SMOKE ALARMS IN ALL BEDROOMS. FBC R314.1 |
| | |
| | 21. NEED SMOKE/CARBON MONOXIDE ALARMS OUTSIDE BEDROOMS. |
| | FBC R 315.1 |
| | |
| | 22. ALL OUTLETS IN BEDROOMS TO BE AFCI PROTECTED. |
| | (RECEPTACLES AND LIGHTING) 210.12A |
| | |
| | HALLWAY: |
| | |
| | 23. NEED 3-WAY SWITCH AT TOP AND BOTTOM OF STAIRS WITH |
| | LIGHT FOR STAIRS. 210.70A2 (A&C) |
| | |
| | BATHROOM: |
| | |
| | 24. NO LIGHT SWITCH IN BATHROOM FOR LIGHT. 210.70A1 |
| | |
| | LAUNDRY ROOM: |
| | |
| | 25. ALL OUTLETS MUST BE AFCI. 210.12A |
| | |
| | 26. WASHING MACHINE MUST ME AFCI/GFCI 210.8A10, 210.12A |
| | NEC |
| | |
| | OUTSIDE SERVICE: |
| | |
| | 27. MINIMUM #4 CU TO COLD WATERPIPE 250.66 NEC |
| | |
| | 28. NEED SERVICE RECEPTACLE WITHIN 50' OF SERVICE |
| | EQUIPMENT. 210.64 NEC |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |