| 2018-10-31 09:12:23 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18090564 |
| | REVIEWED: OCTOBER 30, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. [FBC AMENDED 109]PROVIDE A SEPARATE PERMIT |
| | APPLICATION FOR ONE OF THE UNITS AND SEPARATE THE PLANS |
| | FOR EACH PERMIT. THE 4 TH FLOOR UNIT SHOULD INCLUDE THE |
| | WORK ON THE SOFFIT AND PROVIDE WHAT IS BEING USED FOR |
| | CEILING INSULATION IN THE ATTIC OR INDICATE WHAT IS |
| | EXISTING. |
| | |
| | 2. [FBC AMENDED 109]PROVIDE PROJECT VALUE FOR EACH UNIT |
| | AND PROVIDE CONTRACT FOR EACH AS THE VALUE APPEARS LOW |
| | AT 30,000 FOR THE TWO UNITS. |
| | |
| | 3. [FBC EXISTING 501]THE LEVEL OF ALTERATION SHOULD BE |
| | LEVEL 1 ALTERATION AS STRUCTURAL ELEMENTS AND SYSTEMS |
| | ARE BEING REMOVED AND REPLACED WITH NEW. |
| | |
| | 4. [FBC 107.3.5]PROVIDE EXISTING FLOOR PLAN WITH DEMO |
| | NOTES TO HELP CLARIFY THE SCOPE OF WORK BEING |
| | PERFORMED. |
| | |
| | 5. [FBC A233]PROVIDE ONE BATHROOM DOOR WITH 29 INCH |
| | CLEARANCE. |
| | |
| | 6. PLEASE ADVISE, WHAT FLOORING AND UNDERLAYMENT ARE |
| | PROPOSED? PLEASE ADVISE VIA EMAIL. IF THE UNDERLAYMENT |
| | PRODUCT PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST |
| | REPORTS ON FILE, THE FOLLOWING REPORTS ARE REQUIRED: |
| | |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |