| Plan Review Notes For Permit 18090558 |
| Permit Number |
18090558 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-12-20 05:09:44 | 1) SUBMIT MANUFACTURER'S SPECIFICATIONS AND | | | INSTALLATION MANUALS FOR ALL GAS EQQUIPMENT.A NOTE ON | | | SHT.P-3 FOR THE TANKLESS WATER HEATER IS INSUFFICIENT. | | | EQUIPMENT SHALL BE LISTED AND LABELED PER 2017 FBC-FUEL | | | GAS SEC.301.3, WPB AMEND. TO FBC SEC.. 107.2.1. 2ND | | | REQUEST. | | | 2) SHOW THE DISTANCE FROM THE TANKLESS WATER HEATER TO | | | THE REAR DOOR AND ALL OTHER OPENINGS INTO THE BUILDING. | | | THE TANKLESS WATER HEATER SHALL BE LOCATED IN | | | ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION MANUAL. | | | 2017 FBC-FUEL GAS SEC.305.1. | | | 3) THE COMBUSTION AIR CALCULATIONS THAT HAVE BEEN | | | SUBMITTED DO NOT CORRELATE WITH THE EQUATION IN THE | | | CODE ALTHOUGH THE FINAL TOTAL CFM IS CORRECT. REVISE | | | THE EQUATION NUMBERS TO COMPLY WITH THE CODE. PLEASE | | | REFER TO 2017 FBC-FUEL GAS SEC.304.9. | | | 4) EACH OF THE APPLIANCES SERVED SHALL BE INTERLOCKED | | | WITH THE MECHANICAL AIR SUPPLY SYSTEM TO PREVENT MAIN | | | BURNER OPERATION WHEN THE MECHANICAL AIR SUPPLY SYSTEM | | | IS NOT IN OPERATION. 2017 FBC- FUEL GAS SEC. 304.9.2. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|