| 2018-09-25 10:49:23 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18090558 |
| | 9/25/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-1: RECIRCULATION OF AIR FROM THE KITCHEN |
| | INTO THE BAR AREAS VIA AHU'S 1 & 3 IS PROHIBITED PER |
| | TABLE 403.3.1.1 FOOTNOTE B FBC M. |
| | |
| | 2) M-1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY |
| | AIR SYSTEMS OF THE 5-TON AC-1 & 3 SYSTEMS PER SECTION |
| | 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED |
| | IF THE MANUFACTURER'S SPECIFICATIONS INDICATE THE |
| | SYSTEMS ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF |
| | SUPPLY AIR. |
| | |
| | 3) M-1: THE LOCATION OF THE O/A INTAKE APPEARS TO BE |
| | WITHIN THE MINIMUM 10' REQUIRED CLEARANCE TO THE ALLEY |
| | AND THE PROPERTY LINE- SECTION 401.4 FBC M. |
| | |
| | 4) M-1: PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF |
| | THE NEW CONDENSER ON THE EXITING STAND- SECTION 301.15 |
| | FBC M. |
| | |
| | 5) P-1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE NEW |
| | GAS-FIRED COOKING APPLIANCES- SECTION 304 FBC FG. |
| | |
| | 6) P-1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GAS-FIRE COOKING APPLIANCES- SECTION 623.1 FBC FG. |
| | |
| | 7) ADVISORY: PLEASE REFER TO SECTION 508.1.1 FBC M. |
| | ALTHOUGH THE KITCHEN HOOD IS UNDER A SEPARATE, THE |
| | REQUIREMENT CONCERNING THE TEMPERATURE OF THE MAKEUP |
| | AIR MAY EFFECT THE MAIN HVAC DESIGN. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |