| 2018-09-18 16:54:29 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A 03 - THE OCCUPANCY LOAD CALCULATIONS DO NOT |
| | INDICATE NUMBERS FOR THE KITCHEN OR BAR SERVICE AREA. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS |
| | |
| | |
| | |
| | |
| | 2) THERE ARE NO DIMENSIONS INDICATED TO VERIFY THE |
| | OCCUPANCY LOAD OF THE SEATING AREA. THE BATHROOMS |
| | SHOULD NO BE INCLUDED WITH THE SEATING AREA. |
| | |
| | ADDITIONALLY, THERE ARE NO DIMENSIONS INDCATED BETWEEN |
| | THE SEATS OR EACH AISLE TO ENSURE REQUIRED WIDTHS OR |
| | PASSAGE. |
| | |
| | PER NFPA 101, CHAPTER 12 OR 13, NEW OR EXISTING |
| | ASSEMBLY OCCUPANCIES |
| | |
| | 12.2.5.8 AISLES SERVING SEATING AT TABLES. |
| | |
| | 12.2.5.8.2* THE WIDTH OF AISLES SERVING SEATING AT |
| | TABLES SHALL BE |
| | NOT LESS THAN 44 IN. (1120 MM) WHERE SERVING AN |
| | OCCUPANT LOAD |
| | EXCEEDING 50, AND 36 IN. (915 MM) WHERE SERVING AN |
| | OCCUPANT |
| | LOAD OF 50 OR FEWER. |
| | 12.2.5.8.3* WHERE NONFIXED SEATING IS LOCATED BETWEEN A |
| | TABLE AND |
| | AN AISLE, THE MEASUREMENT OF REQUIRED CLEAR WIDTH OF |
| | THE AISLE SHALL |
| | BE MADE TO A LINE 19 IN. (485 MM), MEASURED |
| | PERPENDICULARLY TO |
| | THE EDGE OF THE TABLE, AWAY FROM THE EDGE OF SAID |
| | TABLE. |
| | 12.2.5.9 APPROVAL OF LAYOUTS. |
| | 12.2.5.9.1 WHERE REQUIRED BY THE AUTHORITY HAVING |
| | JURISDICTION, |
| | PLANS DRAWN TO SCALE SHOWING THE ARRANGEMENT OF |
| | FURNISHINGS OR |
| | EQUIPMENT SHALL BE SUBMITTED TO THE AUTHORITY BY THE |
| | BUILDING |
| | OWNER, MANAGER, OR AUTHORIZED AGENT TO SUBSTANTIATE |
| | CONFORMANCE |
| | WITH THE PROVISIONS OF 12.2.5. |
| | 12.2.5.9.2 THE LAYOUT PLANS SHALL CONSTITUTE THE ONLY |
| | ACCEPTABLE |
| | ARRANGEMENT, UNLESS ONE OF THE FOLLOWING CRITERIA IS |
| | MET: |
| | (1) THE PLANS ARE REVISED. |
| | (2) ADDITIONAL PLANS ARE SUBMITTED AND APPROVED. |
| | (3) TEMPORARY DEVIATIONS FROM THE SPECIFICATIONS OF THE |
| | APPROVED PLANS ARE USED, PROVIDED THAT THE OCCUPANT |
| | LOAD IS |
| | NOT INCREASED AND THE INTENT OF 12.2.5.9 IS MAINTAINED. |
| | |
| | PLEASE REVIEW AND PROVIDE. |
| | |
| | |
| | |
| | 3) SHEET A 04 - 8 SEATS ARE INDCATED ON THE FLOOR PLAN |
| | BY THE LEFT SIDE DOUBLE DOORS. 4 OF THE SEAT ENCROACH |
| | INTO THE PATH OF EGRESS. |
| | |
| | THOSE DOORS ARE NOT REQUIRED TO MEET YOUR EGRESS |
| | DEMAND; HOWEVER, EITHER THOSE DOOR CAN NOT BE INDICATED |
| | AS AN EXIT OR THE CHAIRS AND TABLES WILL NEED TO BE |
| | REMOVED. |
| | |
| | PER NFPA 101, CHAPTER 7, MEANS OF EGRESS. |
| | |
| | 7.1.10 MEANS OF EGRESS RELIABILITY. |
| | 7.1.10.1* MAINTENANCE. MEANS OF EGRESS SHALL BE |
| | CONTINUOUSLY |
| | MAINTAINED FREE OF ALL OBSTRUCTIONS OR IMPEDIMENTS TO |
| | FULL INSTANT |
| | USE IN THE CASE OF FIRE OR OTHER EMERGENCY. |
| | |
| | |
| | |
| | 4) SHEET A 06 - THERE IS KITCHEN COOKING AND HOOD |
| | EQUIPMENT INDICATED. THERE ARE NO INDICATIONS IF THE |
| | NOTED EQUIPMENT IS NEW OR EXISTING. |
| | |
| | PER NFPA 101, CHAPTER 12 OR 13, NEW OR EXISTING |
| | ASSEMBLY OCCUPANCIES |
| | |
| | 12.3.2.2 COOKING EQUIPMENT. COOKING EQUIPMENT SHALL BE |
| | PROTECTED IN ACCORDANCE WITH 9.2.3, UNLESS THE COOKING |
| | EQUIPMENT |
| | IS ONE OF THE FOLLOWING TYPES: |
| | (1) OUTDOOR EQUIPMENT |
| | (2) PORTABLE EQUIPMENT NOT FLUE-CONNECTED |
| | (3) EQUIPMENT USED ONLY FOR FOOD WARMING |
| | |
| | ALL COOKING AND HOOD EQUIPMENT NEW OR EXISTING SHALL BE |
| | INSPECTED AND TESTED FOR COMPLIANCE WITH THE APPLICABLE |
| | CODE. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS |
| | |
| | |
| | |
| | |
| | 5) FIRE SPRINKLER DOCUMENTS ARE INDICATED WITH THE |
| | BACK-UP INFORMATION PACKET . THESE DOCUMENTS ARE |
| | ACCEPTED AS INFORMATIONAL PURPOSES ONLY. |
| | |
| | FIRE SPRINKLER SHOP DRAWINGS SHALL BE SUBMITTED |
| | SEPARATELY FOR APPROVAL. |
| | |
| | |
| | |
| | 6) DOOR INFORMATION DOCUMENTS ARE INDICATED WITH THE |
| | BACK-UP INFORMATION PACKET. THOSE DOCUMENTS ARE |
| | INDICATED WITH HELLBENT CUSTOM GARAGE IN THE TITLE |
| | BLOCKS |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |