| 2018-10-11 06:26:13 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. FBC A 226, 902.1, IT APPEARS THAT THERE ARE TWO |
| | DINING BAR AREAS; REVISE PLAN TO SHOW COMPLIANCE. BAR |
| | HEIGHT IS NOT CLEAR, AND NO ACCESSIBLE PORTION SHOWN. |
| | |
| | 2. FBC A 227, SALES AND SERVICE A POS AND PICK UP AREA |
| | IS SHOWN. REVISE PLAN TO SHOW COMPLIANCE. |
| | |
| | 3. FBC A TABLE 404.2.41(C), THE TWO BATHROOM DOORS SHOW |
| | 12" CLEARANCE ON THE PULL SIDE, BUT IT APPEARS THAT 18" |
| | IS REQUIRED. ALTHOUGH THIS IS EXISTING, PLEASE SEE FBC |
| | A 202.4. IT APPEARS THAT THERE IS ROOM TO MOVE THE LAV |
| | AND MAINTAIN ALL REQUIRED CLEAR FLOOR SPACES. NOTE |
| | THAT, AS INSTALLED, A WHEELCHAIR USER COULD ENTER AND |
| | USE THE BATHROOM BUT MAY BE UNABLE TO EXIT. |
| | |
| | 4. A.04, DOOR SCHEDULE SHOWS "NA" FOR ALL DOORS. FLOOR |
| | PLAN SHOWS THREE NEW DOUBLE DOORS PROPOSED AS WELL AS |
| | EXISTING DOORS AND REFERS TO STRUCTURAL DRAWINGS FOR |
| | THE NEW DOORS. NO STRUCTURAL SHEETS WERE SUBMITTED, |
| | PLEASE PROVIDE. LIFE SAFETY/FLOOR PLAN SHOULD SHOW THE |
| | SIZE OF THE NEW DOORS PROPOSED AS WELL AS PROVIDE |
| | INFORMATION REGARDING EXISTING DOORS, FBC 107, FBC B |
| | 1609, FBC B CHAPTER 10. |
| | |
| | 5. FBC B 1603.1.4, REVISE PLAN TO INCLUDE WIND DESIGN |
| | CRITERIA, INCLUDING DESIGN PRESSURES FOR THE NEW DOORS. |
| | |
| | 6. TO AVOID ANY FIELD CONFLICTS, REVISE THE DOOR |
| | SCHEDULE TO INCLUDE THE PANIC BARS REQUIRED BY FBC B |
| | 1010.1.10 (PER FBC EB 801.3. |
| | |
| | 7. FLORIDA STATUTE 481, DOCUMENTS PREPARED BY AN |
| | ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE TO BE |
| | SIGNED, SEALED DATED ORIGINALS. AT LEAST ONE PAGE WAS |
| | SEALED BUT NOT SIGNED AND DATED. PLEASE CONFIRM ALL |
| | PAGES PRIOR TO RESUBMITTAL. |
| | |
| | 8. THIS PERMIT WILL BE ISSUED WITH PROVISO; PRIOR TO |
| | INSTALLATION, DOOR PRODUCT APPROVALS REVIEWED BY |
| | DESIGNER OF RECORD ARE TO BE SUBMITTED AND ISSUED PRIOR |
| | TO REVIEW. ON THE PRODUCT APPROVAL, INDICATE ADA |
| | THRESHOLD AND PANIC BARS. IF YOU DO NOT AGREE WITH THIS |
| | PROVISO, CONTACT ME PRIOR TO ISSUANCE. |
| | |
| | |
| | |
| | |