| 2018-09-18 14:44:17 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18090472 |
| | REVIEWED: SEPTEMBER 18, 2018 |
| | STRUCTURAL ONLY |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. [FBC 107.2.6]UPLOAD STRUCTURAL CALCULATIONS TO |
| | SUPPORTING FILES (USUALLY 8.5 X 11 DOCUMENT) |
| | |
| | 2. [FBC 1604.5]SHEET S-0.00 VERIFY RISK CATEGORY II IS |
| | THE CORRECT CLASSIFICATION FOR THE BUILDING USE, ADD |
| | WIND DATA TO SHEET S-10.00 AND SHOW WHAT THE MWRFS WILL |
| | BE. |
| | |
| | 3. [FBC AMENDED 106.1]LIVE LOADS POSTED. WHERE THE LIVE |
| | LOADS FOR WHICH EACH FLOOR OR PORTION THEREOF OF A |
| | COMMERCIAL OR INDUSTRIAL BUILDING IS OR HAS BEEN |
| | DESIGNED TO EXCEED 50 PSF (2.40 KN/M2), SUCH |
| | DESIGN LIVE LOADS SHALL BE CONSPICUOUSLY POSTED BY THE |
| | OWNER IN THAT PART OF EACH STORY IN WHICH |
| | THEY APPLY, USING DURABLE SIGNS. IT SHALL BE UNLAWFUL |
| | TO REMOVE OR DEFACE SUCH NOTICES. |
| | |
| | 4. [FBC AMENDED 110.3(A)1.1]A FOUNDATION/FORM BOARD |
| | SURVEY PREPARED AND CERTIFIED BY A REGISTERED SURVEYOR |
| | MAY BE REQUIRED, PRIOR TO APPROVAL OF THE SLAB |
| | INSPECTION. THE SURVEY SHALL CERTIFY PLACEMENT OF THE |
| | BUILDING ON THE SITE, ILLUSTRATE ALL SURROUNDING |
| | SETBACK DIMENSIONS AND SHALL BE AVAILABLE AT THE JOB |
| | SITE FOR REVIEW BY THE BUILDING INSPECTOR. |
| | |
| | 5. SHEET S-2.02A-PT-THE DESIGNATION FOR SW-2 SAYS SW-1. |
| | UPDATE SW-2 DESIGNATION(THIS IS THE ONLY INSTANCE I |
| | SAW). |
| | |
| | 6.SHEETS S-7.01 AND S-702 HAVE QUESTION MARKS WHERE |
| | DATA WAS TO BE ENTERED. PLEASE ENTER DATA WHERE THERE |
| | ARE QUESTION MARKS ON THESE TWO SHEETS. |
| | |
| | 7. IS THERE ANY REINFORCING ON FOUNDATION SLAB FOR |
| | RE-ENTRANT CORNERS? I DON?T SEE NOTES OR DETAIL IF |
| | BEING USED. |
| | |
| | 8. IS THERE ANY ACCESS TO THE ATTIC SPACES? PLEASE SHOW |
| | OF ROOF PLANS IF APPLICABLE. |
| | |
| | 9. IF ANY PLUMBING OR ELECTRICAL IS RUN WITHIN |
| | STRUCTURE, SUBMIT THOSE SHEETS SO THEY WILL BECOME |
| | APART OF STRUCTURAL PERMIT. |
| | |
| | 10. SUBMITTALS: |
| | |
| | A [FBC 1014]GUARDS AND HANDRAILS. |
| | PROVIDE HANDRAIL/GUARDRAIL ENGINEERING, OR INDICATE |
| | THAT YOU WOULD LIKE IT DEFERRED. |
| | |
| | B. [FBC AMENDED 107.2.1.2]PROVIDE METAL PAN STAIRCASE |
| | ENGINEERING, OR INDICATE THAT IT WILL BE A DEFERRED |
| | SUBMITTAL. |
| | |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |