Plan Review Notes
Plan Review Notes For Permit 18090472
Permit Number 18090472
Review Stop B
Sequence Number 1
Notes
Date Text
2018-09-18 14:44:17****CORRECTIONS****
 W.P.B. PERMIT: 18090472
 REVIEWED: SEPTEMBER 18, 2018
 STRUCTURAL ONLY
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. [FBC 107.2.6]UPLOAD STRUCTURAL CALCULATIONS TO
 SUPPORTING FILES (USUALLY 8.5 X 11 DOCUMENT)
  
 2. [FBC 1604.5]SHEET S-0.00 VERIFY RISK CATEGORY II IS
 THE CORRECT CLASSIFICATION FOR THE BUILDING USE, ADD
 WIND DATA TO SHEET S-10.00 AND SHOW WHAT THE MWRFS WILL
 BE.
  
 3. [FBC AMENDED 106.1]LIVE LOADS POSTED. WHERE THE LIVE
 LOADS FOR WHICH EACH FLOOR OR PORTION THEREOF OF A
 COMMERCIAL OR INDUSTRIAL BUILDING IS OR HAS BEEN
 DESIGNED TO EXCEED 50 PSF (2.40 KN/M2), SUCH
 DESIGN LIVE LOADS SHALL BE CONSPICUOUSLY POSTED BY THE
 OWNER IN THAT PART OF EACH STORY IN WHICH
 THEY APPLY, USING DURABLE SIGNS. IT SHALL BE UNLAWFUL
 TO REMOVE OR DEFACE SUCH NOTICES.
  
 4. [FBC AMENDED 110.3(A)1.1]A FOUNDATION/FORM BOARD
 SURVEY PREPARED AND CERTIFIED BY A REGISTERED SURVEYOR
 MAY BE REQUIRED, PRIOR TO APPROVAL OF THE SLAB
 INSPECTION. THE SURVEY SHALL CERTIFY PLACEMENT OF THE
 BUILDING ON THE SITE, ILLUSTRATE ALL SURROUNDING
 SETBACK DIMENSIONS AND SHALL BE AVAILABLE AT THE JOB
 SITE FOR REVIEW BY THE BUILDING INSPECTOR.
  
 5. SHEET S-2.02A-PT-THE DESIGNATION FOR SW-2 SAYS SW-1.
 UPDATE SW-2 DESIGNATION(THIS IS THE ONLY INSTANCE I
 SAW).
  
 6.SHEETS S-7.01 AND S-702 HAVE QUESTION MARKS WHERE
 DATA WAS TO BE ENTERED. PLEASE ENTER DATA WHERE THERE
 ARE QUESTION MARKS ON THESE TWO SHEETS.
  
 7. IS THERE ANY REINFORCING ON FOUNDATION SLAB FOR
 RE-ENTRANT CORNERS? I DON?T SEE NOTES OR DETAIL IF
 BEING USED.
  
 8. IS THERE ANY ACCESS TO THE ATTIC SPACES? PLEASE SHOW
 OF ROOF PLANS IF APPLICABLE.
  
 9. IF ANY PLUMBING OR ELECTRICAL IS RUN WITHIN
 STRUCTURE, SUBMIT THOSE SHEETS SO THEY WILL BECOME
 APART OF STRUCTURAL PERMIT.
  
 10. SUBMITTALS:
  
 A [FBC 1014]GUARDS AND HANDRAILS.
 PROVIDE HANDRAIL/GUARDRAIL ENGINEERING, OR INDICATE
 THAT YOU WOULD LIKE IT DEFERRED.
  
 B. [FBC AMENDED 107.2.1.2]PROVIDE METAL PAN STAIRCASE
 ENGINEERING, OR INDICATE THAT IT WILL BE A DEFERRED
 SUBMITTAL.
  
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  